STA06
ACT. VALUE
OUTPUT 3
Actual value
Output 3
0...100
%
0
22:033
STA07
ACT. VALUE
OUTPUT 4
Actual value
Output 4
0...100
%
0
22:034
STA08
ACT. VALUE
OUTPUT 5
Actual value
Output 5
0...100
%
0
22:035
STN1
STATUS STA-
TION CAS.
Status during
cascade
operation
Status of the station in the FW
cascade manager: Digit 1:
Sequential number for the sta-
tion, range 0...5, 0: Station not
available
Digits 2...4: Control signal "s" of
the CM for this station:
n
0: Off
n
1..100: Overmodulation with s
in %
n
101: Not ready, no power
n
102: Standby
n
103: Controlling
00...1103
-
0
02:123
STN2
STATUS STA-
TION CAS.
Status during
cascade
operation
00...2103
-
0
STN3
STATUS STA-
TION CAS.
Status during
cascade
operation
00...3103
-
0
STN4
STATUS STA-
TION CAS.
Status during
cascade
operation
00...4103
-
0
STN5
STATUS STA-
TION CAS.
Status during
cascade
operation
00...5103
-
0
PRI
PRIMARY
PRI01
TANK TOP
TEMP
Temperature
of consumers
at top TXO
Display for the current tempera-
ture in the buffer/tank at top.
0...120
°C
0
00:015
PRI02
TANK TOP
SETPOINT
TEMP
Setpoint
temperature
of the con-
sumers at
top
Display for the calculated set-
point in the buffer/tank. This
value is calculated from the DHW
setpoint and the flow rate-
dependent temperature loss.
0...120
°C
25
00:015
PRI03
TANK BOTTOM
TEMP
Temperature
of consumers
at bottom
TXU
Display for the current tempera-
ture in the buffer/tank at bottom.
0...120
°C
0
00:016
PRI04
PRIM. FLOW
TEMP
Flow tem-
perature PWT
TPV
Display for the current flow tem-
perature on the primary plate
heat exchanger, heat source.
0...120
°C
0
21:023
PRI05
PRIM. RETURN
TEMP
Return tem-
perature PWT
TPR
Display for the current return
temperature on the primary plate
heat exchanger.
0...120
°C
0
21:024
ES 5941
Info and menu parameters
08/2020 Item no. 215790 EA no. 1321
Operating instructions
25