5.1
Values, information level
The visible values vary depending on the chosen
hydraulic variant and option and are dependent on
the code that is entered in the “Key” column, see
Ä
Chapter 4.5 “Entering the code” on page 18.
Menu
Description
Range
Unit
Key
ID
Info
STA
STATUS
STA01
STATUS
Status of the
domestic hot
water
n
0: Shut down.
n
2: Thermal disinfection/
comfort mode.
n
5: Fault.
n
6: Tapping/WW tap.
n
7: Warning.
n
8: Setpoint reduction.
n
10: Reheating.
n
11: Interruption of charging.
n
14: Standby station in the cas-
cade.
0...11
-
0
02:052
STA02
CIRC. CALI-
BRATION
Status, cali-
bration of cir-
culation flow
rate
n
0: Inactive – No calibration
made to date, or last calibra-
tion no longer valid.
n
1...8: Active, Measurement
1...8. If measurements 1..4 ok,
transfer to 9, otherwise con-
duct measurements 5...8 and
then evaluate.
n
9: Calibration carried out suc-
cessfully.
n
10: Start
n
11: Error – Flow despite pump
being switched off.
n
12: Error – Flow rate fluctua-
tions too great when the pump
is switched on.
0
STA03
INFO THM.
DISINFECTION
Information
about
thermal dis-
infection
Information about thermal disin-
fection with specification of the
date on which this was carried
out successfully.
yyyy
dd:mm
-
0
02:127
STA04
SPEED PRIM.
PUMP
Actual value
Output 1
0...100
%
0
22:031
STA05
OUTPUT CIRC.
PUMP
Actual value
Output 2
0...100
%
0
22:032
ES 5941
Info and menu parameters
08/2020 Item no. 215790 EA no. 1321
Operating instructions
24