In order for all functions to operate flawlessly, calibration of the flow
rate in the circulation line is always to be carried out when using a
circulation pump. ZIR 06 CIRC. CALIBRATION (
Ä
Chapter 6.5 “Calibration
of the circulation volume” on page 39).
n
Check that all temperature setpoints are set correctly.
n
Check that it is possible to take a reading of the temperatures
(actual values) of the connected sensors.
n
Check that the temperatures (actual values) of the connected
sensors are plausible.
n
Check that hot water preparation is possible by means of a tapping
process.
n
Enter setting specific to the hydraulic variant or adjustment of the
controller.
Calibration of the flow rate
Measures after commissioning
ES 5941
Commissioning
08/2020 Item no. 215790 EA no. 1321
Operating instructions
13