SEK
SECONDARY
SEK01 DHW TEM-
PERATURE
Domestic hot
water tem-
perature TWW
Display for the current tap tem-
perature on the secondary plate
heat exchanger.
0...120
°C
0
00:067
SEK02 DHW
TEMP.SET-
POINT
Domestic hot
water set-
point tem-
perature TWW
Display for setpoint
BAS01 DHW
TEMP.SETPOINT or LEG01 TEMP
TERM.DISINFECTION
if legionella
protection is active, and fixed
10 °C frost protection in standby.
0...120
°C
25
01:067
SEK03 DHW COLD
WATER TEMP
Domestic
cold water
temperature
TKW
Display for the current domestic
cold water inlet temperature on
the secondary plate heat
exchanger.
0...120
°C
0
00:068
SEK04 FLOW RATE
DHW
Flow rate
FLOW
Display for the current water flow
rate on the secondary plate heat
exchanger.
0...999.9
l/min 0
00:069
SEK05 CIRCULATION
TEMP
Circulation
temperature
TBZ
Display for the current circulation
temperature, local value
according to the choice of sensor
ZIR03 SENSOR CIRCULATION
from
TKW, TBZ or TWW.
0...120
°C
0
00:118
SEK06 SETPOINT
CIRCULATION
T
Circulation
setpoint tem-
perature
Display for the circulation set-
point calculated from
BAS01 DHW
TEMP.SETPOINT
minus
ZIR01
TEMP.REDUCE TSET CIRC.
.
0...120
°C
25
01:118
AUS
REPORTING
AUS02 MAX FLOW
RATE 24H
Maximum flow
rate in 24h
0...999.9
l/min
25
02:126
AUS03 ENERGY DHW
Partial energy
requirement E
Display for the energy require-
ment for domestic hot water
preparation in kWh. The counter
returns to 0 once 1 Mwh is
reached. This allows the total
yield to be read in MWh and the
partial yield to be read in kWh.
0...999.9
kWh
0
23:006
AUS04 TOTAL
ENERGY DHW
Total energy
requirement
GES
0...999.9
MWh
0
23:013
AUS05 PRIM. PUMP
OPERATING H
Operating
hours of the
primary pump
FRIWA
0...999.9
h
0
02:120
ES 5941
Info and menu parameters
08/2020 Item no. 215790 EA no. 1321
Operating instructions
26