Alarms
The table below describes the alarms you may encounter and how they are reset.
Alarm
Range
Alarm Trigger
Alarm Reset
Fan Failure
Normal, Alarm
Occurs when the fan input detects
that the fan is not running after a
30-second grace period after the
fan has been activated.
The cause of the emergency condition
must be resolved and the controller
must be reset.
Smoke
Normal, Alarm
Occurs when the smoke alarm
input detects the presence of
smoke.
The cause of the emergency condition
must be resolved and the controller
must be reset.
Mixed Air Low Limit
Normal, Alarm
Occurs when the mixed air tem-
perature drops below the Low
Limit that has been set, indicating
a freeze condition.
The cause of the emergency condition
must be resolved and the controller
must be reset.
Filter
Normal, Alarm
Occurs when the Filter Alarm input
detects that the filter needs to be
replaced.
Automatic when the dirty filter is
replaced.
Indoor Air Quality
Normal, Alarm
Occurs when the IAQ sensor
detects inadequate indoor air qual-
ity.
Automatic when air quality returns
within normal parameters.
Heating Failure
Normal, Alarm
Occurs when Supply Air tempera-
ture is
Supply Heat Limit
degrees
from the setpoint 10 minutes after
entering heating mode.
The cause of the emergency condition
must be resolved.
Cooling Failure
Normal, Alarm
Occurs when Supply Air tempera-
ture is
Supply Cool Limit
degrees
from the setpoint 10 minutes after
entering cooling mode.
The cause of the emergency condition
must be resolved.
Heat Stuck On
Normal, Alarm
Occurs when the mode is primary
off or primary fan only if the supply
air temperature does not drop
below 150
°F after five minutes.
The cause of the emergency condition
must be resolved.
Maintenance
Normal, Alarm
Occurs when the fan, heating, or
cooling operating hours have
exceeded their Runtime limit.
To clear the alarm, a user must enter
a new value for the alarm limit or reset
the accumulated times to zero.