iWorx® VPU2
505-010-2, Effective: April 29, 2014
35
© 2014 Taco Electronic Solutions, Inc.
Inputs
The Inputs screen displays the current values of the VPU2’s inputs. These values cannot be changed.
Outputs
This screen displays the current values of the VPU2's outputs. These values cannot be changed.
This screen also displays the current status of each device in the VPU2's group. Each device is displayed on its own
line, and is identified as being off, in heating mode, or in cooling mode.
Input
Range
Description
Outside Temp
-29 to 230
°F (-34.4 to 110
°C)
The outside air temperature com-
municated through the LCI from
the ASM controller.
Smoke Detector
Normal, Smoke
Status of the smoke detector.
Fan Status
Off, On
Status of the fan proof switch.
Low Limit
Normal, Freeze
Status of the mixed air low limit
indication switch.
Filter Status
Normal, Dirty
Status of the filter status switch.
Indoor Air Qual
Normal, Alarm
Status of the IAQ alarm sensor
when defined as Digital.
Occupancy Mode
Occupied,
Unoccupied,
Bypass
Occupancy mode of the controller.
Supply Air Temp
-29 to 230
°F (-34.4 to 110
°C)
Temperature of the supply air duct.
Mixed Air Temp
Temperature of the mixed air ple-
num.
Return Air Temp
Temperature of the return air duct.
Return Air Humidity
0.00 to 100.00%
Humidity inside the return air duct.
Static Pressure
0.00 to 5.00” WC (0 to 0.181 PSI)
(0 to 1246
Pa)
Pressure in the supply air duct.
Inside Enthalpy
0.0 to 60.0 BTU/lb
0.0 to 139.6 kjoule/kg
Calculated inside air enthalpy.
Out Enthalpy
2.0 to 60.0 BTU/lb
3.0 to 139.6 kjoule/kg
Calculated outside air enthalpy.
IAQ
0 to 4000 ppm
Reading of the indoor air quality
sensor when defined as Analog.
Output
Range
Description
Mode
Heat,
Cool,
Off,
Fan,
Free Cooling,
Dehumid,
Shut Down
Operating Mode
Heat Output
0.00% to 100.00%
Current state of the heating output.
VFD Output
0.00% to 100.00%
Current state of the VFD output.
Cool Output
0.00% to 100.00%
Current state of the cooling output.