Floating SP Heating/Cooling
Displays all of the floating point heating or cooling settings and provides access to edit these parameters from a single
screen.
Economizer
Displays all the economizer settings and provides access to edit these parameters from a single screen.
Ki
0 to 100.00%
0.05%
Integral gain of the economizer's
P+I control loop.
Min AO Voltage
0.0 to 10.0 V
0.0 V
Minimum output voltage for modu-
lation.
Max AO Voltage
0.0 to 10.0 V
0.0 V
Maximum output voltage for modu-
lation. If set to 0 Modulation is dis-
abled.
Setting
Range
Default
Description
Kp
0.0 to 100.00% per F
5.00%
Proportional gain of the economiz-
ers P+I control loop.
Ki
0 to 100.00%
0.05%
Integral gain of the economizer's
P+I control loop.
Travel Time
0.0 to 600 sec
0
Total time it takes for the valve to
travel from fully closed to fully
open. If set to 0 floating point is dis-
abled.
Deadband
0.0 to 100.0%
10%
The desired setpoint must be this
far or greater from the actual posi-
tion before modulating the actuator.
Setting
Range
Default
Description
Type
Disabled,
2 St
Unocc
On,
2 St
Unocc
Off,
Mod
Unocc.
On,
Mod
Unocc.
Off
Disabled
If using an economizer, set this
field to a value that describes the
type of economizer and whether it
should be enabled during unoccu-
pied periods.
Setpoint
40.00 to 70.00
°F
(4.44 to 21.11 °C)
55.00
°F
(12.78
°C)
Setpoint used for controlling the
modulated economizer.
Min Fresh Air
0.00 to 100.00%
10.0%
Minimum fresh air position for the
modulated economizer.
Kp
0.0 to 100.00% per F
5.00%
Proportional gain of the economiz-
ers P+I control loop.
Ki
0 to 100.00%
0.05%
Integral gain of the economizer's
P+I control loop.
Min AO Voltage
0.0 to 10.0 V
0.0 V
Minimum output voltage for modu-
lated economizer.
Max AO Voltage
0.0 to 10.0 V
10.0 V
Maximum output voltage for modu-
lated economizer.
Setting
Range
Default
Description