Free Cooling
Displays all the free cooling settings and provides access to edit these parameters from a single screen.
Dehumidification
Displays all the dehumidification settings and provides access to edit these parameters from a single screen.
Runtime Limits
Displays all the runtime limit settings and provides access to edit these parameters from a single screen.
Backup Occ Time / Unocc Time
Displays all the backup schedule settings and provides access to edit these parameters from a single screen.
Setting
Range
Default
Description
Type
Rtn Air Humidity,
Global Humidity,
DryBulb temp
Rtn Air Humidity Type of free cooling comparison to
be performed.
Enthalpy Offset
0.0 to 60.0 BTU/lb
(0.0 to 139.86 kjoule/kg
5.0 BTU/lb
11.6 kjoule/kg
Difference between inside enthalpy
and outside enthalpy that enables
or disables the economizer.
Drybulb Offset
0.0 to 20.0
°F
(0.0 to 11.1
°C)
5.00
°F
(2.78
°C)
Difference between zone tempera-
ture and outside temperature that
enables or disables the econo-
mizer.
Setting
Range
Default
Description
Type
Occupied,
Always enabled
Occupied
Defines when dehumidification is
enforced.
Setpoint
0.00 to 100.00%
0%
Humidity Setpoint
Shutoff offset
0 to 10.0
°F
(0 to 5.56
°C)
2.00
°F
(1.11 °C)
Difference between zone tempera-
ture and outside temperature that
enables or disables the econo-
mizer.
Setting
Range
Default
Description
Cooling
0 to 65535 hours
1000 hours
Runtime limit for cooling after
which a maintenance alarm is gen-
erated.
Heating
0 to 65535 hours
1000 hours
Runtime limit for heating after
which a maintenance alarm is gen-
erated.
Fan
0 to 65535 hours
1000 hours
Runtime limit for the fan after which
a maintenance alarm is generated.
Setting
Range
Default
Description
Hour
0 to 23
0
Hour to start occupied/unoccupied
times.
Minute
0 to 59
0
Minute to start occupied/unoccu-
pied times.