Pressure Settings
Displays all of the Static pressure settings and provides access to edit these parameters from a single screen.
Staged Cooling/Heating
Displays all of the staged heating or cooling settings and provides access to edit these parameters from a single
screen.
Modulated Heating/Cooling
Displays all of the modulated heating or cooling settings and provides access to edit these parameters from a single
screen.
Setting
Range
Default
Description
Setpoint
-2.5 to 5.00”
W.C.
(-623 to 1246
Pa)
1.0”
W.C.
(249
Pa)
Setpoint for supply air static pres-
sure.
IAQ Setpoint
-2.5 to 5.00”
W.C.
(-623 to 1246
Pa)
1.5”
W.C.
(374
Pa)
Setpoint for supply air static pres-
sure used when an IAQ alarm is
present.
Kp
0.0 to 100.00% per F
5.00%
Proportional gain of the economiz-
ers P+I control loop.
Ki
0 to 100%
per
0.1”
W.C.
0.05%
Integral gain of the economizer's
P+I control loop.
Minimum Output
0.0 to 10.0 V
0.0 V
Minimum voltage output for the fan
VFD.
Maximum Output
0.0 to 10.0 V
10.0 V
Maximum voltage output for the fan
VFD.
Press Min
-2.5 to 5.00”
W.C.
(-623 to 1246
Pa)
0.00”
W.C.
(0
Pa)
Static pressure to report when the
analog input receives 0
volts.
Press Max
-2.5 to 5.00”
W.C.
(-623 to 1246
Pa)
2.00”
W.C.
(498
Pa)
Static pressure to report when the
analog input receives 10
volts.
Soft Start Rate
0.00 to 100.00%
0.00%
Percentage of fan output increase
per second.
Setting
Range
Default
Description
Stages
0 to 2 (heating)
0 to 4 (cooling)
2 - Heating
4 - Cooling
Number of stages that are avail-
able. Set to zero to disable staged
cooling.
Stage Control Band
0.00 to 10.00
°F
(0.00 to 5.56
°C)
1.00
°F
(0.56
°C)
Value used to modify the calcu-
lated cooling setpoints to form the
temperature range I which local
cooling is enabled.
Stage Time
0 to 255
minutes
5 minutes
The interval between sequencing
of stages.
Setting
Range
Default
Description
Kp
0.0 to 100.00% per F
5.00%
Proportional gain of the economiz-
ers P+I control loop.