iWorx® VPU2
10
505-010-2, Effective: April 29, 2014
© 2014 Taco Electronic Solutions, Inc.
Figure 4: Typical VPU2 Wiring - Example C
Connecting Input Devices
Return Humidity (RAH)
To connect the Return Air Humidity sensor to the unit, connect the positive wire from the sensor to RAH (T19) and the
other wire to the adjacent common (T18). The sensor must be of the 0-10 Volt type.
If global indoor air humidity readings are being provided over the network, it is not necessary to attach a return air
humidity sensor directly to the VPU2.
Mixed Air (MAT)
To connect the Mixed Air thermistor to the unit, attach one wire from the thermistor to MAT (T17) and the other wire to
the adjacent common (T18). The thermistor used must be 10K Precon Type III.