iWorx® VPU2
505-010-2, Effective: April 29, 2014
25
© 2014 Taco Electronic Solutions, Inc.
Figure 10: Modulated Staging with 2 Stages; 1st Stage Modulating
Cooling Sequence
The controller provides support for either four compressor stages of cooling or one floating point or 0-10V modulating
cooling output (valve or variable speed circulator). You can specify which type of cooling you are using through config-
uration parameters.
Cooling Stages
The cooling sequence is initiated when the current operating mode calls for cool. The cooling compressor stages are
sequenced based on the supply temperature, the cooling setpoint and the control band. When the supply air tempera-
ture rises above the cooling setpoint plus the control band, a stage is turned on. If the supply air temperature remains
above the control band for an additional time-period, the next available stage is turned on. If all zone temperature read-
ings are within 0.5
°F of their setpoints, the next stage does not cycle on. This cycle continues until all available stages
have been energized.