505-010-2, Effective: April 29, 2014
41
© 2014 Taco Electronic Solutions, Inc.
IAQ Settings
Displays all the IAQ settings and provides access to edit these parameters from a single screen.
IAQ Sensor
Displays all the IAQ sensor settings and provides access to edit these parameters from a single screen.
Cutoff Temp
Displays all the OAT cutoff settings and provides access to edit these parameters from a single screen. A value of -4.0
disables the cutoff temperature setting.
Setting
Range
Default
Description
IAQ Delay Time
0 to 1000
minutes
5 minutes
Time delay before reporting an IAQ
alarm.
Temp Reset Limit
0 to 15
°F
(0 to 8.3
°C)
5 °F
(2.78°C)
Temperature Reset Limit to ensure
comfort temperature during IAQ
Alarm conditions.
Deadband
0 to 400 ppm
0 ppm
Deadband to allow the IAQ to
recover from the alarm condition.
Setting
Range
Default
Description
Min
0 to 4000 ppm
0 ppm
Minimum ppm sensor setting.
Max
0 to 4000 ppm
0 ppm
Maximum ppm sensor setting.
Setpoint
0 to 4000 ppm
0 ppm
Setpoint.
Offset
0 to 4000 ppm
0 ppm
Offset to the sensor reading.
Setting
Range
Default
Description
Max OAT Heat
-7.6 to 122
°F
(-22 to 50
°C)
-4
°F
Outside air temperature above
which heating is disabled.
Max OAT Cool
-7.6 to 122
°F
(-22 to 50
°C)
-4
°F
Outside air temperature below
which cooling is disabled.
Max OAT Econ
-7.6 to 122
°F
(-22 to 50
°C)
-4
°F
Outside air temperature above
which the economizer is disabled.
Min OAT Econ
-7.6 to 122
°F
(-22 to 50
°C)
-4
°F
Outside air temperature below
which the economizer is disabled.
SAT Cooling Limit
45 to 65
°F
(7.22 to 18.3
°C)
55
°F
(12.8
°C)
Supply air temperature below
which additional cooling will not be
enabled.