Commissioning
Displays VPU2 settings that are useful during commissioning of the unit.
Setpoints
This screen displays the heating and cooling setpoints used by the VPU2 controller. Use the up and down arrow keys
to select a value to change, then use
-
or
+
to increase or decrease the value (or utilize
USE KEYS
to directly enter
the desired value). Press
Save
to save your changes or
Back
to return to the Setup screen.
Supply Temp Reset Curve
Displays all of the Supply Temp Reset settings and provides access to edit these parameters from a single screen.
Setting
Range
Default
Description
Override Mode
Off,
Fan VFD %,
Fan VFD 0%,
Fan VFD 100%
Off
Set to any value besides “Off” to
place the controller into that over-
ride mode.
Fan VFD Percentage
0.00% to 100.00%
0.00%
Fan setting to use when the con-
troller is placed in “Fan VRD %”
override mode.
Setpoint
Range
Default
Description
Cooling Setpoint
45.0 to 65
°F
(7.22 to 18.33
°C)
55.00
°F
(12.78
°C)
Temperature setpoint for the cool-
ing mode.
Heating Setpoint
55.00 to 130.0
°F
(12.8 to 54.4
°C)
90.00
°F
(32.22
°C)
Temperature setpoint for the heat-
ing mode.
Supply Cool Limit
0.00 to 30.0
°F
(0.00 to 16.6
°C)
10
°F
(5.5
°C)
Minimum temperature change from
cooling setpoint in 10 minutes to
avoid a cooling failed alarm.
Supply Heat Limit
0.00 to 30.0
°F
(0.00 to 16.6
°C)
10
°F
(5.5
°C)
Minimum temperature change from
heating setpoint in 10 minutes to
avoid a heating failed alarm.
Setting
Range
Default
Description
Min Differential
0.00 to 30.0
°F
(0.00 to 16.6
°C)
0.00
°F
(0.00
°C)
Differential at or below which the
supply air is at it coolest.
Max Differential
0.00 to 30.0
°F
(0.00 to 16.6
°C)
0.00
°F
(0.00
°C)
Differential at or above which the
supply air is at it warmest.
Cool Setp Low
45.0 to 65.0
°F
(7.22 to 18.3
°C)
45.0
°F
(7.22
°C)
Lowest cooling SP when the zone
is at its warmest.
Cool Setp High
45.0 to 65.0
°F
(7.22 to 18.3
°C)
65.0
°F
(18.3
°C)
Highest cooling SP when the zone
is at its coolest.
Heat Setp Low
55.0 to 130.0
°F
(12.8 to 54.4
°C)
80.0
°F
(26.67
°C)
Lowest heating SP when the zone
is at its warmest.
Heat Setp High
55.0 to 130.0
°F
(12.8 to 54.4
°C)
130.0
°F
(54.4
°C)
Highest heating SP when the zone
is at its coolest.