T1/T2 (raw):
Signal run times along complete signal path including pipe
wall and transducer enclosure
dt (raw):
Measured time difference of T1/T2 (raw)
XDCR (DCR=Transducer):
Signal run time within transducer
Pipe delay:
Signal run time within pipe wall
qp:
Compensation factor considering changes in temperature (and
therefore changes in speed of sound of fluid).
Coating delay:
Delay in signal run time generated by coating (if
applicable)
Lambda Corr.:
Delay can be manually edited (not recommended, only for maintenance)
by multiples of wave length of signal.
Delay Corr:
Shows Lambda Corr in useconds
Table 6 Data in diagnostic menu 3