Ziegler-Nichols method for the optimization of a PID controller:
Parameters
: Setpoint, P-Band, Reset time, Derivative time
The point of intersection of the tangent with the respective axis will
result in the parameters a and L.
Consult the manual of the control unit for connecting and program
-
ming details. Choose control upwards or downwards.
Control upwards or downwards
Setpoint:
User-defined process value for the selected parameter.
P-Band:
Range below (upwards control) or above (downwards con
-
trol) the set-point, within the dosing intensity is reduced from 100% to
0% to reach the setpoint without overshooting.
5.2.1.43
Control Parameters:
if Parameters = Cond. 1(sc)
5.2.1.43.10
Setpoint
Range: 0.000 –3000
S
5.2.1.43.20
P-Band:
Range: 0.000 –3000
S
5.2.1.43
Control Parameters:
if Parameters = Cond. 2(cc)
5.2.1.43.11
Setpoint
Range: 0.000 –3000
S
5.2.1.43.21
P-Band:
Range: 0.000 –3000
S
A
B
X
Response to maximum control output
Tangent on the inflection point
Time
Xp
Tn
Tv
= 1.2/a
= 2L
= L/2
X
Y
B
A
L
a