AMI Codes-II TC
Default Values
A-96.250.631 / 280219
103
Parameter:
.....................................................................Calc. Dichl.
Settings: Actuator: .......................................................... Frequency
Settings: Pulse Frequency: .............................................120/min.
Settings: Control Parameters: Setpoint:....................... 20.00 ppm
Settings: Control Parameters: P-band: .......................... 0.10 ppm
Parameter:
...................................................................Temperature
Settings: Actuator: .......................................................... Frequency
Settings: Pulse Frequency: .............................................120/min.
Settings: Control Parameters: Setpoint:............................... 30 °C
Settings: Control Parameters: P-band: .................................. 1 °C
Parameter:
.................................................................. Sample Flow
Settings: Actuator: .......................................................... Frequency
Settings: Pulse Frequency: .............................................120/min.
Settings: Control Parameters: Setpoint:........................... 200 B/s
Settings: Control Parameters: P-band: .............................. 20 B/s
Parameter:
................................................................................... pH
Settings: Actuator: .......................................................... Frequency
Settings: Pulse Frequency: .............................................120/min.
Settings: Control Parameters: Setpoint:................................ 7 pH
Settings: Control Parameters: P-band: .............................. 0.1 pH
Common settings
Settings: Control Parameters: Reset time:...........................0 Sec
Settings: Control Parameters: Derivative Time: ...................0 Sec
Settings: Control Parameters: Control Timeout:................... 0 Min
Settings: Actuator: ................................................ Time proportional
Cycle time: ............................................................................ 60 s
Response time: ..................................................................... 10 s
Settings: Actuator ......................................................... Motor valve
Run time: ............................................................................... 60 s
Neutral zone: ...........................................................................5%
If Function = Timer:
Mode:.................................................................................... Interval
Interval: ................................................................................ 1 min
Mode: ........................................................................................daily
Start time:........................................................................ 00.00.00
Mode:..................................................................................... weekly
Calendar; Start time: ....................................................... 00.00.00
Calendar; Monday to Sunday:.................................................. Off
Run time: ...............................................................................10 Sec
Delay: ......................................................................................5 Sec