24
2.13 Function
Week Disinfect
Under disinfection mode, the unit will immediately start to heat water up to 65°C to kill the Legionella
Pneumophila inside water tank. ‘ ’ icon will light on the display screen during disinfection. Unit will
quit disinfection mode if water temperature is higher than 65°C and extinguish the icon.
Vacation function
After pressing ‘Vacation’ button, unit will automatically heat water to 15°C for the purpose of energy
saving during vacation days.
Query function
For the convenience of maintenance and debug, query function is available by pressing 2 buttons
together: ‘E-HEATER’+’DISINFECT’, then system running parameters will be shown one by one with
following sequence by each pushing of ‘UP’ or ‘DOWN’ button.
No.
Hour low bit
Min. high bit
Min. low bit
Item
Explanation
1
Temperature
T5U
2
Temperature
T5L
3
Temperature
T3
4
Temperature
T4
5
Temperature
TP
6
Temperature
Th
7
Current
Compressor
8
Last error code
9
Previous 1st error or protection
code
10
Previous 2nd error or protection
code
11
Software number
TCO and ATCO
The power of compressor and E-heater will be automatically switch on or switch off by TCO and
ATCO.
If the water temperature is higher than 78°C, the ATOC will automatically shut off the power of the
compressor and E-heater, and turn it on if the temperature falls down below 68°C.
If the water temperature is higher than 85°C, the TOC will automatically shut off the power of the
compressor and E-heater, it should be re-turn manually.