40
case c
i) Ts = 50°C and T4 = 1°C then Tstop = 60°C
T5U < min (45 ; 55) T5U < 45°C
ii) : Ts = 50°C and T4 = -3°C then Tstop = 45°C
T5U < min (45 ; 40) T5U < 40°C
2)
When in below condition, the the heat pump stop:
T5L ≥ min (Ts ; Tstop)
Example :
i) : Ts = 50°C and T4 = 1°C then Tstop = 60°C
T5L ≥ min (50 ; 60) T5L ≥ 50°C
Water is heated only by
Heat Pump, until T5L reaches the
desired temperature (50°C)
Water is heated only by Heat Pump, until T5L
reaches the stop-temperature (45°C).
Now heat pump stops and
the unit automatically
activates the resistance “E-heater” to reach the
desired temperature (50°C).