5-10
Sun Server X2-4 Service Manual • April 2013
FIGURE 5-4
Removing the Fan Board
▼
Install the Fan Board
1. Unpack the replacement fan board unit and place it on an antistatic mat.
2. Remove the fan board cable and power cables from the faulty fan board unit
and plug them into the fan board on the replacement fan board unit.
3. Reinstall the fan board unit (
FIGURE 5-5
):
a. Insert the fan board unit into the chassis, moving it down and toward the
front.
b. Reposition the front memory riser guide, routing the fan board and power
cable through the riser guide.
c. Plug the fan board cable and power cable into the connectors on the
motherboard.
Содержание Fire X4470 M2
Страница 1: ...Sun Server X2 4 formerly Sun Fire X4470 M2 Service Manual Part No E20784 06 April 2013...
Страница 14: ...xiv Sun Server X2 4 Service Manual April 2013...
Страница 38: ...2 12 Sun Server X2 4 Service Manual April 2013...
Страница 54: ...3 16 Sun Server X2 4 Service Manual April 2013...
Страница 84: ...4 30 Sun Server X2 4 Service Manual April 2013...
Страница 106: ...5 22 Sun Server X2 4 Service Manual April 2013 FIGURE 5 11 Installing the Motherboard...
Страница 153: ...Appendix A Server Specifications A 3...
Страница 154: ...A 4 Sun Server X2 4 Service Manual April 2013...
Страница 156: ...B 2 Sun Server X2 4 Service Manual April 2013 B 1 BIOS Main Menu Selections FIGURE B 1 BIOS Main Menu...
Страница 158: ...B 4 Sun Server X2 4 Service Manual April 2013 FIGURE B 3 BIOS Advanced Menu CPU Configuration First Screen...
Страница 160: ...B 6 Sun Server X2 4 Service Manual April 2013 FIGURE B 6 BIOS Advanced Menu ACPI Configuration Screen...
Страница 161: ...Appendix B BIOS Setup Utility Menus B 7 FIGURE B 7 BIOS Advanced Menu AHCI Configuration Screen...
Страница 162: ...B 8 Sun Server X2 4 Service Manual April 2013 FIGURE B 8 BIOS Advanced Menu I O Virtualization Screen...
Страница 166: ...B 12 Sun Server X2 4 Service Manual April 2013 B 3 BIOS PCIPnP Menu Selections FIGURE B 15 BIOS PCIPnP Menu First Screen...
Страница 167: ...Appendix B BIOS Setup Utility Menus B 13 FIGURE B 16 BIOS PCIPnP Menu Second Screen...
Страница 168: ...B 14 Sun Server X2 4 Service Manual April 2013 B 4 BIOS Boot Menu Selections FIGURE B 17 BIOS Boot Menu...
Страница 170: ...B 16 Sun Server X2 4 Service Manual April 2013 B 5 BIOS Security Menu Selections FIGURE B 20 BIOS Security Menu...
Страница 171: ...Appendix B BIOS Setup Utility Menus B 17 B 6 BIOS IO MMIO Menu Selections FIGURE B 21 BIOS IO MMIO Menu...
Страница 172: ...B 18 Sun Server X2 4 Service Manual April 2013 FIGURE B 22 BIOS IO MMIO Menu IO MMIO Ration Configuration Screen...
Страница 173: ...Appendix B BIOS Setup Utility Menus B 19 B 7 BIOS Chipset Menu Selections FIGURE B 23 BIOS Chipset Menu...
Страница 174: ...B 20 Sun Server X2 4 Service Manual April 2013 FIGURE B 24 BIOS Chipset Menu South Bridge Configuration Screen...
Страница 175: ...Appendix B BIOS Setup Utility Menus B 21 B 8 BIOS Exit Menu Selections FIGURE B 25 BIOS Exit Menu...
Страница 176: ...B 22 Sun Server X2 4 Service Manual April 2013...
Страница 182: ...C 6 Sun Server X2 4 Service Manual April 2013...