7 Related Parameters
25
b1-18
Voltage
Reference
Source
N/A
N/A
Sets the input source for the DC bus
voltage reference.
0: LED operator
1: Control circuit terminal (analog input)
2: MEMOBUS/Modbus communications
3: Option card
7: Input voltage based control 1
8: Input voltage based control 2
Default: 0
Range:
0 to 3, 7, 8
o2-01
LOCAL/
REMOTE
Key Function
Selection
N/A
YES
Enables/Disables the option LOCAL/
REMOTE key.
0: Disabled
1: Enabled
Default: 1
Range: 0, 1
o2-02
STOP Key
Function
Selection
YES
YES
Enables/Disables the operator panel
STOP key when the unit is operated form
external sources (not operator).
0: Disabled
1: Enabled
Default: 1
Range: 0, 1
o2-05
Frequency
Reference
Setting
Method
Selection
YES
YES
Selects if the ENTER key press is
required when inputting the frequency
reference by the digital operator.
0: Data/Enter key must be pressed to
enter a frequency reference.
1: Data/Enter key is not required. The
frequency reference is adjusted by the up
and down arrow keys.
Default: 0
Range: 0, 1
o2-06
Operation
Selection
when LED
Operator
Option is
Disconnected
YES
YES
Sets unit action when the option is
removed in LOCAL mode or with b1-02
= 0.
0: The drive, converter, or regenerative
unit will continue operation.
1: The drive, converter, or regenerative
unit will trigger a fault (oPr) and the
motor will coast to stop.
Default: 0
Range: 0, 1
No.
Name
Unit
Description
Values
SF-520
HF-520