7 Related Parameters
26
o3-01
Copy
Function
Selection
YES
YES
This parameter controls the copying of
parameters to and from the option.
0: COPY SELECT (no function)
1: All parameters are copied from the unit
to the LED Operator Option.
2: All parameters are copied from the
LED Operator Option to the drive,
converter, or regenerative unit.
3: Parameter settings in the drive,
converter, or regenerative unit are
compared to those in the LED Operator
Option.
Note:
When using the copy function, the
drive model number (o2-04), software
number (U1-14), and control method
(A1-02) must match or an error will
occur.
Default: 0
Range: 0 to 3
o3-02
Copy
Allowable
YES
YES
Enables or disables reading of unit
parameter settings.
0: Disabled - Read not allowed
1: Enabled - Read allowed
Default: 0
Range: 0, 1
<1> b1-01 = 4 and b1-02 = 3 are not compatible with the SF-520.
No.
Name
Unit
Description
Values
SF-520