55
-
The maintenance symbol
on the status bar indicates that an output test is active.
-
You can see the present output value at the value for “Output signal UX1.”
-
A unit is indicated below the value (e.g. voltage V).
Conclude Output Test
Conclude the output test as follows if the testing of the output is completed:
1.
Press the control knob to select the test value.
2.
Turn the control knob to the left until “---%” is displayed.
3.
Press the control knob to confirm the setting.
-
Control of UX1 for testing is concluded; the maintenance symbol on the status bar disappears; after a brief
period, the display of the test value returns to the original display “Unused.”
4.
Go to the title of the diagnostic page to conduct additional diagnostics or select “Back” to return to the topic
list.
17.8.3.2 Adjust / Repair
The following is displayed on the Adjust / Repair pages:
1.
Complete parameter list
2.
Commissioning wizard.
3.
Refresh operator unit ***
*** The list entry “Refresh operator unit” is displayed if changes are
made on the “complete parameter list” or commissioning wizard that
impacts the device pages.
Complete Parameter List
The complete parameter list has the following structure:
- The title of the parameter list page (Heating or DHW).
- 3 operating line are displayed per parameter list page. Current
page and total pages are displayed to the right of the title if a title
includes more than 3 operating lines.
- You can scroll through the parameter list pages on highlighted
page titles; left for topics & right within a topic.
- The operating line numbers are sorted chronologically in
ascending order via topics and pages.
- The heat pump controller manual includes an overall parameter
list and a detailed explanation on all parameters.
A long press of the knob ( > 3 seconds) jumps from any page to the “expert view start page” (diagnostics
page).