54
9.
Complete the same process for the rest of the 5 digit OEM password.
10.
You will receive feedback on a successful login, that you confirm with “continue.”
11.
The user symbol ( ) with the corresponding level is displayed on the status bar.
Within the expert level, there are two additional chapters:
-
Diagnostics
-
Adjust / Repair
17.8.3.1 Diagnostics
The following is displayed on the Diagnostics pages:
1. Input / Output Test.
2. Communication.
3. Simulation.
4. Producer.
5. Consumers.
6. Error History.
7. Versions.
Operating and use of diagnostic pages is illustrated below using the
input
/ output test as an example.
Example Input / Output Test
To test the Output UX1, complete the following:
1.
Select the diagnostic page
2.
Turn the control knob and select “Input / Output Test.”
3.
Press the control knob
– ‘Input / Output Test’ opens:
The title of the first page of the input/output test is preselected. The associated parameters with operating
lines are displayed in the work area.
4.
Press the control knob to select the title.
5.
Turn the control knob until you see the input or output to be tested
– In this case ‘Output UX.’
’
Conduct Output Test
Limitations do not act during the output test:
-
Ensure that the components controlled during the output test cannot result in undesired operating
states.
1.
Press the control knob to go to the work area.
2.
Turn the control knob until the setting valve for ‘Output text EX1’ is highlighted.
3.
Press the control knob to select the test value.
4.
Turn the control knob and enter the test value (e.g 20%).