Connecting Systems to Power Through PDUs
11-6
Stratus ftServer 29x0, 49x0, and 69x0 Systems: Site Planning and Installation Guide
(R786)
Connecting Systems to Power Through PDUs
N O T E
Do not connect a PDU or peripheral components to a
Stratus-qualified UPS, which is sized only for the ftServer
system.
1. From the front of the system, make sure that the CPU-I/O enclosures are fully
inserted into the shelf unit by tightening the thumbscrews, if necessary.
2. Locate two black power cables and two labels, A and B.
3. Connect the A-side and B-side PDUs to
separate
AC power sources. For each
PDU, do the following:
a. At the back of the cabinet, attach the IEC 320-C19 connector end of the
country-specific external power cord (number 5 in
) to the single
PDU inlet connector on the right side of the PDU.
b. Connect the country-specific connector end to a power source.
c. Attach the appropriate label to the power cable to indicate A- or B-side power.
shows how to connect PDUs to ftServer systems and directly to
power sources.
4. Locate one black and one gray power cable (
jumper
).
5. Connect the IEC-C13 end of the
gray
power cable (number 4) to the receptacle on
the top CPU-I/O enclosure. (Lift the small power-cord locking bar above the
receptacle to insert the power cord into the enclosure.) Connect the other end of
the gray cable to the
top
PDU.
6. Connect the IEC-C13 end of the
black
cable (number 3) to the receptacle on the
bottom CPU-I/O enclosure. Connect the other end of the black cable to the
bottom
PDU.
7. If applicable, repeat steps
for additional systems.
shows the color-coded power cords connected to the systems and PDUs.