INSTaLLaTION
Commissioning
www.stiebel-eltron.com
WPL 15 IKS | WPL 25 IK |
53
12.7 WPMme commissioning report
No.
Parameter
Setting range
Standard
System value
1
Enter code
0000 to 9999
1000
2
Language
English
3
Contrast
-10 to +10
0
4
Display
Actual return
5
Emergency mode
ON / OFF
OFF
6
Heat up programme
ON / OFF
OFF
6a
Low end temperature (AHP)
20...40 °C, incr 0.5 K
25.0 °C
6b
Low end temperature duration (AHP)
0 to 5 days
2 days
6c
Maximum heat-up temperature (AHP)
27...50 °C, incr 0.5 K
40.0 °C
6d
Maximum temperature duration (AHP)
0 to 10 days
0 days
6e
Increase / day (AHP)
1 to 10 K/day
1 K/day
7
Summer mode
ON / OFF
ON
7a
Building type (SB)
0 v 3
1
7b
Outside temperature (SB)
1 to 30 °C, incr 0.5 K
20.0 °C
8
Pump cycles
ON / OFF
OFF
8a
Min. outside temperature (PZ)
-10.0 °C
8b
Max. outside temperature (PZ)
10.0 °C
8c
Cycles, min. outside temperature (PZ)
288
8d
Cycles, max. outside temperature (PZ)
48
9
Pump constant run
ON / OFF
ON
10
Fixed temperature
OFF/20...60 °C
OFF
11
Silent mode
11 a
Reduced output
OFF / 99..50%
OFF
11 b
Heat pump OFF
ON / OFF
OFF
12
Max. return temperature
20.0 to 60.0 °C
60.0 °C
13
Max. flow temperature, heating
20.0 to 70.0 °C
70.0 °C
14
Max. flow temperature, domestic hot water
20.0 to 70.0 °C
65 °C
15
Max. mixer temperature
20.0 to 55.0 °C
50 °C
16
Mixer dynamic
30 to 240
100
17
Frost protection temperature
-10.0 to 10.0 °C
4.0 °C
18
Remote control selection
Heating circuit 1 to 2
HEATING CIRC 1
19
FE correction (FE)
-5.0 K to 5.0 K
0.0 K
20
Room influence (FE)
0 to 20
5
21
Dual mode temperature, heating
-20 to 40 °C
-15 °C
22
Delay, DHC heating
0 to 120 min
60 min
23
Maximum DHC stages, heating
0 to 3
3
24
Circulation pump output, heating
20 to 100 %
80 %
25
DHW output in summer
5 to 12 kW
10,5 kW
26
DHW output in winter WPL 15 IKS / WPL 25 IK
5 to 12 kW
6 kW / 10,5 kW
27
Dual mode temperature, DHW
-20 to 40 °C
-15 °C
28
Delay, DHC DHW
0 to 60 min
60 min
29
Maximum DHC stages, DHW
1 .. 3
3
30
Circulation pump output, DHW
20 to 100 %
60 %
31
DHW ECO
ON / OFF
OFF
32
DHW hysteresis
1.0 to 10.0 K
3.0 K
33
DHW correction
0.0 to 5.0 K
3.0 K
34
DHW heating
ON / OFF
ON
35
Pasteurisation mode
ON / OFF
OFF
36
Flow proportion, heating circuit 1
0 to 100 %
50 %
37
P component (proportional component, heating)
0.0 to 10.0 %/K
1.5 %/K
38
Controller dynamic (integral component, heating)
0 to 500 K min
400 K min
39
Design temperature, heating
OFF / -25.0 to 5 °C
-15.0 °C
40
Minimum compressor runtime
0 to 20 min
10 min
41
Power-OFF
OFF / ON / 0 to 3
42
Idle time
3 to 120 min
10 min
43
Remaining idle time
Display only
44
Quick start
ON / OFF
OFF
45
Relay test
46
LCD test
47
Fault list
48
Software version WPMme
49
MFG software