INSTaLLaTION
appliance installation
www.stiebel-eltron.com
WPL 15 IKS | WPL 25 IK |
27
Example: Strip foundation
1
2
4
3
6
5
A
D
00000
24
41
9
A Depth of frost line
1 Refrigerant suction gas line
2 Refrigerant, liquid line
3 Condensate drain
4 Foundation
5 Gravel bed
6 Drainage pipe
Example: Wall mounting bracket
A
≥250
3
1
2
6
4
5
D
00000
19
56
9
A Depth of frost line
1 Refrigerant suction gas line
2 Refrigerant, liquid line
3 Condensate drain
4 Gravel bed
5 Wall mounting bracket
6 Drainage pipe
f
f
Observe the static limits of the building wall and the wall
mounting bracket.
The appliance must be securely fastened to the wall mounting
bracket.
Example: T-support
A
1
3
2
7
4
6
5
D
00000
19
56
8
A Depth of frost line
1 Refrigerant suction gas line
2 Refrigerant liquid line
3 Condensate drain
4 Foundation
5 T-support
6 Gravel bed
7 Drainage pipe
f
f
Observe the static limits of the T-support used.
10.3 Condensate drain
A condensate drain connector is fitted to the defrost pan at the
factory to enable the condensate to drain off.
1
26
�0
3�
01
�1
82
2
1 Condensate drain
f
f
Secure a condensate hose to the condensate drain.
f
f
Protect the condensate hose against frost with sufficient
thermal insulation.
f
f
Run the condensate hose without loops and with a con-
tinuous fall to the drainage pipe (see diagram in chapter
„Siting“).
f
f
If necessary, trim the condensate hose.
!
Material damage
Ensure the condensate hose is not kinked. Route the hose
with a slope.