40
www.stiebel-eltron.CoM
coolIng wItH tHE HEat pUmp SyStEm
Passive cooling
with passive cooling, the low
temperature of the groundwater
or that of the upper earth crust is
transferred to the heating system via
a heat exchanger. the heat pump
compressor will not be started, i.e. the
heat pump remains passive.
Active cooling
During active cooling, the cooling
output of the heat pump (cold side) is
transferred to the heating system. the
heat pump compressor will be started,
i.e. the heat pump becomes active.
Procedure for allowing passive
cooling:
Calculating the cooling load
– to VDi 2078
– in accordance with a standard
form
– in accordance with the m² area
of the living space (factor)
Determining the cooling capacity
of the heat sink
– geothermal probe
– groundwater
sizing the distribution system
– underfloor heating system
– fan convectors
Heat pump installation
– wPC cool
– wPF
Design information:
the cooling capacity of the heat sink
can be seen in the table on page 41.
For example, two geothermal probes
with a depth of 94 metres can transfer
approx. 7.2 kw to the ground (wPC 13
cool).
the heat transfer by the heat sink
must not exceed the cooling load
of the building. the required room
temperature cannot be achieved if the
cooling load is greater. if necessary,
some rooms must be excluded from
the cooling demand to achieve the
required room temperature in the
other rooms.
Average temperatures underground (°C)
Drilling depth (m)
exposed site
Urban area
High location
0
9.5
9.5
3.2
25
11.3
12.5
8.0
50
12.0
13.5
8.7
75
12.8
14.5
9.5
100
13.5
15.5
10.2
125
14.3
16.5
11.0
150
15.0
17.5
11.7
175
15.8
18.5
12.5
200
16.5
19.5
13.2
Temperature curve underground
Cooling of buildings
Disabled
enabled
Passive systems
Active systems
Utilisation of natural heat sinks
Cool ground / cool night air
Utilisation of storage effects
Utilisation of refrigerators
*+1 °C temperature rise every 33 m
Dep
th (m)
Содержание Heat pumps
Страница 97: ...97 www stiebel eltron COM Notes ...
Страница 110: ...110 www stiebel eltron COM Notes ...
Страница 116: ...116 www stiebel eltron COM Notes ...
Страница 124: ...124 www stiebel eltron COM Notes ...
Страница 182: ...182 www stiebel eltron COM Notes ...
Страница 183: ...183 www stiebel eltron COM Accessories for heating heat pumps ...
Страница 234: ...234 www stiebel eltron COM WPF E mono mode without buffer cylinder WPF E mono mode with DHW heating ...
Страница 235: ...235 www stiebel eltron COM WPF E mono mode with low loss header WPF E mono mode with DHW heating and low loss header ...
Страница 247: ...247 www stiebel eltron COM DHW heat pumps ...