![STIEBEL ELTRON Heat pumps Скачать руководство пользователя страница 173](http://html1.mh-extra.com/html/stiebel-eltron/heat-pumps/heat-pumps_technical-manual_1376699173.webp)
173
www.stiebel-eltron.CoM
HEatIng SyStEm connEctIon wpw 7/10/13/18
Heating system connection
install the heat utilisation system
(HUs) in accordance with the design
documentation. For standard heating
systems integrate the heat pump
into the water side according to
standard circuits (see appendix).
Prior to connecting the heat pump,
check the heating system for leaks,
flush it thoroughly, then fill and vent
it thoroughly. ensure the correct
connection of the heating flow and
return. Flexible pressure hoses are
recommended to reduce structure-
borne noise transmission on the water
side. the required circulation pump
is integrated into the heat pump. the
adjacent table shows the pipe cross-
section. Provide thermal insulation in
accordance with local regulations.
Power supply
You may need to notify your local
power supply company of the heat
pump connection. All electrical
installation work, particularly earthing
measures, must be carried out in
accordance with local and national
regulations and the requirements of
your local power supply company.
the connection must comply with
the power connection diagram. Also
observe the installation instructions.
terminals are located inside the heat
pump control panel and become
accessible by removing the front cover.
the following are connected there:
the heat pump power supply (400 V)
the heating cartridge power supply
(400 V) (internal Hs 2)
the well pump power supply (400 V)
the control power supply (230 V)
the enable signal (230 V)
heating circuit pump (230 V)
the mixing valve (230 V)
various sensors and remote control
units
WPW with buffer cylinder SBP 100 and DHW heating
Heat pumps type WPW with integral circulation pump UP 25-60
Heat pump
Flow rate
residual head
Copper pipe
type
m³/h
hPa
mm
wPw 7
0.6
280
22 x 1.0
wPw 10
0.8
280
28 x 1.5
wPw 13
1.1
100
28 x 1.5
wPw 18
1.4
100
28 x 1.5
WPW
b1
temperature sensor heat pump flow l
Power supply
b2
temperature sensor heat pump return on
Compressor signal
t (ww)
temperature sensor, DHw
Ks
brine pump signal
t(A)
outside temperature sensor
Cooling Cooling mode
t(MK)
temperature sensor, mixer circuit
MKP
Mixer circuit pump
Fern1
remote control
eVU
enable signal
Fern3
remote control
M(A)
Mixer open
H
bUs high
M(Z)
Mixer closed
l
bUs low
HKP
Heating circuit pump
–
bUs ground
QKP
source circuit pump
+
bUs (not connected)
3/n/Pe
230V ~ 50Hz
Domestic meter
Control phase l
w/o power-oFF
period
Control phase l´
with power-oFF
period
3/n/Pe
400V ~ 50Hz
Heat pump
electricity meter
Electrical specification of the heat pumps
Heat pump
Power
consumption
Max. operating
current
starting
current r start
Power cable
Fuse
protection
type
kw
A
A
mm²
A
wPw 7
3.7
6.1
25
5 x 2.5 *
C 16A all poles
wPw 10
4.5
7.7
27
5 x 2.5 *
C 16A all poles
wPw 13
5.9
9.5
28
5 x 2.5 *
C 16A all poles
wPw 18
6.2
12.0
29
5 x 2.5 *
C 16A all poles
* Cable cross-section acc. to type of routing (observe VDe 0298-4 [or local regulations])
26
_0
3_
01
_0
47
4
Содержание Heat pumps
Страница 97: ...97 www stiebel eltron COM Notes ...
Страница 110: ...110 www stiebel eltron COM Notes ...
Страница 116: ...116 www stiebel eltron COM Notes ...
Страница 124: ...124 www stiebel eltron COM Notes ...
Страница 182: ...182 www stiebel eltron COM Notes ...
Страница 183: ...183 www stiebel eltron COM Accessories for heating heat pumps ...
Страница 234: ...234 www stiebel eltron COM WPF E mono mode without buffer cylinder WPF E mono mode with DHW heating ...
Страница 235: ...235 www stiebel eltron COM WPF E mono mode with low loss header WPF E mono mode with DHW heating and low loss header ...
Страница 247: ...247 www stiebel eltron COM DHW heat pumps ...