![STIEBEL ELTRON Heat pumps Скачать руководство пользователя страница 35](http://html1.mh-extra.com/html/stiebel-eltron/heat-pumps/heat-pumps_technical-manual_1376699035.webp)
35
www.stiebel-eltron.CoM
HEat pUmpS wItHoUt bUffEr cylIndEr
Installation without buffer cylinder
if heat pumps in a heating system are
installed without a buffer cylinder,
observe the following information:
A constant heat pump flow rate is
required to enable the heat pump
to function correctly. this must be
at least 20% of the nominal flow
rate. Particularly for air | water heat
pumps, other higher minimum flow
rates may be required. observe the
product documentation. Constant
flow rates are primarily achieved with
area heating systems, where no zone
valves are used in case of several
heating circuits. to avoid contravening
the energy savings Act [Germany],
an appropriate dispensation must
be applied for from the building
Authorities if no zone valves are
installed. For example, if there are
no zone valves installed in the living
room, the room temperature can be
captured by the Fe 7 / FeK remote
controller, which in turn complies
with the requirements of the energy
savings Act [Germany].
with air | water heat pumps, the
minimum flow rate specified in the
following table must be ensured.
Minimum flow rate
Heat pump
m³/h
wPl 10
0.4
wPl 13 e
1.0
wPl 18 e
1.2
wPl 23 e
1.4
wPl 13 cool
1.2
wPl 18 cool
1.7
wPl 23 cool
2.2
wPl 33
1.4
Mono-mode brine | water heat pump without buffer cylinder
Reference room without zone valve
Room temperature regulation via heat
pump remote control FE 7
Overflow valve ÜV required to prevent
flow noise
Minimum circulation volume on the heating side 20% of the nominal flow rate of the heat pump
Mono-energetic air | water heat pump without buffer cylinder
Reference room without zone valve
Room temperature regulation via heat
pump remote control FE 7
Overflow valve ÜV required to prevent
flow noise
Observe the minimum water circulation volume on the heating side.
Содержание Heat pumps
Страница 97: ...97 www stiebel eltron COM Notes ...
Страница 110: ...110 www stiebel eltron COM Notes ...
Страница 116: ...116 www stiebel eltron COM Notes ...
Страница 124: ...124 www stiebel eltron COM Notes ...
Страница 182: ...182 www stiebel eltron COM Notes ...
Страница 183: ...183 www stiebel eltron COM Accessories for heating heat pumps ...
Страница 234: ...234 www stiebel eltron COM WPF E mono mode without buffer cylinder WPF E mono mode with DHW heating ...
Страница 235: ...235 www stiebel eltron COM WPF E mono mode with low loss header WPF E mono mode with DHW heating and low loss header ...
Страница 247: ...247 www stiebel eltron COM DHW heat pumps ...