Well installation
Heat source system
A supply and return well or soakaway
well are required for utilising
groundwater as heat source. the
required flow rate (water volume of
the wss) is stated in the heat pump
specification. A pump test lasting
several days should ascertain whether
the water volume required by the heat
pump is available. establish the water
quality by means of a water analysis.
the dirt trap with a mesh size of
0.6 mm that is part of the standard
delivery of the heat pump protects
the heat pump evaporator against
foreign matter that could settle. install
it immediately at the heat pump inlet.
As the volume and quality of the
water remain unchanged, the heat
pump process will not interfere in
the sense of the water Household Act
[Germany]. However, the heat pump
operator must apply to the relevant
authority for usage of the water [if
applicable].
Well construction
the wells should be at least 15 m
apart. the return or soakaway well
returns the extracted water volume to
the groundwater. when constructing
the wells, ensure that the cooled
water that enters the return well will
not come into contact with the supply
well. the well hole depth depends on
the level of the ground water table.
experience has shown that most wells
for heat pumps require a depth of
between 5 and 15 m. Always route
the pipelines with a slope towards the
wells.
Well heat pump system
boiler room
return
well
supply
well
idle water
level
supply
water
level
1 Pre-duct, well
2 Duct cover, well
3 Connection head, well
4 supply pipe
5 Downpipe
6 submersible pump
7 shut-off valves
8 Dirt filter
9 Pressure gauge
10 thermometer
11 Draw-off valves
Содержание Heat pumps
Страница 97: ...97 www stiebel eltron COM Notes ...
Страница 110: ...110 www stiebel eltron COM Notes ...
Страница 116: ...116 www stiebel eltron COM Notes ...
Страница 124: ...124 www stiebel eltron COM Notes ...
Страница 182: ...182 www stiebel eltron COM Notes ...
Страница 183: ...183 www stiebel eltron COM Accessories for heating heat pumps ...
Страница 234: ...234 www stiebel eltron COM WPF E mono mode without buffer cylinder WPF E mono mode with DHW heating ...
Страница 235: ...235 www stiebel eltron COM WPF E mono mode with low loss header WPF E mono mode with DHW heating and low loss header ...
Страница 247: ...247 www stiebel eltron COM DHW heat pumps ...