Heating system connection
install the heat utilisation system
(HUs) in accordance with the design
documentation. For standard heating
systems integrate the heat pump
into the water side according to
standard circuits (see appendix).
Prior to connecting the heat pump,
check the heating system for leaks,
flush it thoroughly, then fill and vent
it thoroughly. ensure the correct
connection of the heating flow and
return. Flexible pressure hoses are
recommended to reduce structure-
borne noise transmission on the water
side. the required circulation pump
is integrated into the heat pump. the
adjacent table shows the pipe cross-
section. Provide thermal insulation in
accordance with local regulations.
WPF M with buffer cylinder SBP 200 and DHW heating
Heat pumps type WPF.M without integral circulation pump
Heat pump
Flow rate
Circulation pump
Copper pipe
type
m³/h
type
mm
wPF 10 M
0.9
UP 26-60
28 x 1.5
wPF 13 M
1.2
UP 25 - 60
28 x 1.5
wPF 16 M
1.4
UP 25-80
28 x 1.5
Содержание Heat pumps
Страница 97: ...97 www stiebel eltron COM Notes ...
Страница 110: ...110 www stiebel eltron COM Notes ...
Страница 116: ...116 www stiebel eltron COM Notes ...
Страница 124: ...124 www stiebel eltron COM Notes ...
Страница 182: ...182 www stiebel eltron COM Notes ...
Страница 183: ...183 www stiebel eltron COM Accessories for heating heat pumps ...
Страница 234: ...234 www stiebel eltron COM WPF E mono mode without buffer cylinder WPF E mono mode with DHW heating ...
Страница 235: ...235 www stiebel eltron COM WPF E mono mode with low loss header WPF E mono mode with DHW heating and low loss header ...
Страница 247: ...247 www stiebel eltron COM DHW heat pumps ...