137
www.stiebel-eltron.CoM
HEatIng SyStEm connEctIon wpf 5/7/10/13/16 E/cool
Heating system connection
install the heat utilisation system
(HUs) in accordance with the design
documentation. For standard heating
systems integrate the heat pump
into the water side according to
standard circuits (see appendix).
Prior to connecting the heat pump,
check the heating system for leaks,
flush it thoroughly, then fill and vent
it thoroughly. ensure the correct
connection of the heating flow and
return. the required circulation pumps
are integrated into the heat pump. the
adjacent table shows the pipe cross-
section. Provide thermal insulation in
accordance with local regulations.
Check the expansion volume of the
heat source and the heating system
relative to the size of the integral
expansion vessels. An additional
expansion vessel may need to be
installed.
Power supply
You may need to notify your local
power supply company of the heat
pump connection. All electrical
installation work, particularly earthing
measures, must be carried out in
accordance with local and national
regulations and the requirements of
your local power supply company.
the connection must comply with
the power connection diagram. Also
observe the installation instructions.
terminals are located inside the heat
pump control panel and become
accessible by removing the front cover.
the following are connected there:
the heat pump power supply
(400 V)
the heating cartridge power supply
(400 V) (internal Hs 2)
the control power supply (230 V)
the enable signal (230 V)
heating circuit pump (230 V)
the mixing valve (230 V)
various sensors and remote control
units.
WPF..E/cool with buffer cylinder SBP 200 and DHW heating
Heat pump type WPF..E/cool with integral heating circuit pump
Heat pump
Flow rate
residual head
Copper pipe
type
m³/h
hPa
mm
wPF 5 e
1.0
515
22 x 1.0
wPF 7 e
1.4
451
28 x 1.5
wPF 10 e
1.8
365
28 x 1.5
wPF 13 e
2.4
205
28 x 1.5
wPF 16 e
2.9
205
28 x 1.5
WPF..E
b1
temperature sensor heat pump flow l
Power supply
b2
temperature sensor heat pump return on
Compressor signal
t (ww)
temperature sensor, DHw
Ks
brine pump signal
t(A)
outside temperature sensor
Cooling Cooling mode
t(MK)
temperature sensor, mixer circuit
MKP
Mixer circuit pump
Fern1
remote control
eVU
enable signal
Fern3
remote control
M(A)
Mixer open
H
bUs high
M(Z)
Mixer closed
l
bUs low
HKP
Heating circuit pump
–
bUs ground
QKP
source circuit pump
+
bUs (not connected)
buffer buffer primary pump
3/n/Pe
230V ~ 50Hz
Domestic meter
Control phase l w/o
power-oFF period
Control phase l´
with power-oFF
period
3/n/Pe
400V ~ 50Hz
Heat pump
meter
Electrical specification of the heat pumps
Heat
pump
Power
consumption
on/oFF
current max.
starting current
r start
Power
cable
Fuse
protection
type
kw
A
A
mm²
A
wPF 5 e
2.9
3.3
25
5 x 2.5 *
C 16A all poles
wPF 7 e
3.7
6.1
25
5 x 2.5 *
C 16A all poles
wPF 10 e
4.5
7.7
27
5 x 2.5 *
C 16A all poles
wPF 13 e
5.9
9.5
28
5 x 2.5 *
C 16A all poles
wPF 16 e
6.2
12.0
29
5 x 2.5 *
C 16A all poles
* Cable cross-section acc. to type of routing (observe VDe 0298-4 [or local regulations])
Содержание Heat pumps
Страница 97: ...97 www stiebel eltron COM Notes ...
Страница 110: ...110 www stiebel eltron COM Notes ...
Страница 116: ...116 www stiebel eltron COM Notes ...
Страница 124: ...124 www stiebel eltron COM Notes ...
Страница 182: ...182 www stiebel eltron COM Notes ...
Страница 183: ...183 www stiebel eltron COM Accessories for heating heat pumps ...
Страница 234: ...234 www stiebel eltron COM WPF E mono mode without buffer cylinder WPF E mono mode with DHW heating ...
Страница 235: ...235 www stiebel eltron COM WPF E mono mode with low loss header WPF E mono mode with DHW heating and low loss header ...
Страница 247: ...247 www stiebel eltron COM DHW heat pumps ...