09/24999842
21
For smoke heat extraction and daily ventilation for 24 V DC linear drives and chain motors
Please keep these operating instructions for future reference and maintenance.
Subject to technical modifications. Diagram is not binding.
SHE control panel TRZ Basic 4A/UP
SHE control panel TRZ Basic 4A/UP
Function
Smoke extraction system preferably for electromechanical openings in
stairways. Opening of the smoke vent flaps in case of fire. Closing of the
smoke vent flaps via closed-function.
Opening and closing for daily ventilation. Smoke vent flaps* as dome lights,
folding skylights or windows with 24 V DC linear drives or chain motors.
* (hereafter referred to only as “windows”).
Special features
• function “daily ventilation”
• 1 SHE group and 1 ventilation group
• 24 V power supply, emergency power batteries and charging unit, parallel
operation, 72 hours of functioning guaranteed in case of power failure
• line monitoring of alarm circuits (autom. detectors and SHE man. call points)
• line monitoring of the connected drives
• adjustable extraction limit
• adjustable automatic ventilation, closing after 10 min.
• optical malfunction alarm
• separately fused power input 230 V AC / 50 Hz
• all outputs protected against shortcircuit
• temperature controlled battery charged voltage
• sheet steel housing for flush mounting
• flush mounting option with facing frame hinged door, lockable
• conforms to current state-of-the-arts standards
• processor controlled
• extension capabilities due to optional available plug-in modules
• TÜV type tested
TRZ Basic 4A/UP
Stiftleiste für
Erweiterungen
Pin ledge for
extensions
RWA-Reset
SHE Reset
Control board
Steuerplatine
Steckbrücken /
J1 Lüftungstaster “Sonderfunktion”
J2 Lüftungszeitautomatik
Jumper
J1 Vent switch “special function”
J2 Automatic control ventilation time
Betrieb OK
RWA Auf
Störung
Operating ok
SHE open
Malfunction
OK
!
TRZ Basic 4A/UP
Anzeige /
Display
Jumper
J1 Vent switch, “special
function”, J2 Automatic
control ventilation time
Pin ledge
for
extensions
Display
Operating OK
SHE Open
Malfunction
Control board
SHE Reset