Start up procedure and trial run
Test emergency power supply
Disconnect mains power supply, the green LED
OK
“operating OK” goes out (after max. 100 sec). The yellow LED
-
malfunction - flashes. In case of power failure, the windows close immediately.
Press the “open” switch of the vent switch, no window reaction. Press the switch SHE “open”, the windows open.
The red LED
- SHE activation - is shining, the green LED
OK
“operating OK” not lit up. Press the switch “closed” of
the SHE manual call point, the windows close completely. The red LED
“SHE-activation” goes out. The yellow LED
“malfunction” flashes. Re-connect mains voltage, the green LED
OK
“operating OK” is shining after a moment. Reset
the activation.
Test automatic detectors
Make react the automatic detector (test spray):
the red LED in the autom. detector is shining.
The red LED
- “SHE activation” is shining.
The green LED
OK
- “operating OK” is shining.
The windows open completely.
Press the switch “closed” of the vent switch, no window reaction. Get rid of the smoke in the detectors, elsewhere new
activation! Press the switch “SHE Reset” in the control panel TRZ Basic, the windows close completely and the
automatic detector is reset. The red detector LED goes out.
Test automatic ventilation control
Jumper J2 is plugged in. Press the switch “Open” of the vent switch, the windows open completely. After 10 min. the
windows close automatically, automatic ventilation control is OK.
Completion work
Insert the glass panes in all SHE manual call points. Close the control panel door. Stick on the service contact telephone
number.
Note
: If the trial run fails, repeat the initial start up procedure!
Troubleshooting
Display - operating OK - is not shining
• A malfunction has occurred (see flash code), eliminate the malfunction.
• Mains power connection out of order:
- check mains supply lead/voltage.
- check mains fuse.
• Batteries out of order:
- check battery fuse.
- check battery connection.
- defective batteries, to be replaced.
The drives open without pressing a switch
• SHE manual call point incorrectly connected or defective, check and correct.
• autom. detector soiled, replace.
• due to a fault vent switch in permanent contact.
• a malfunction has occurred.
• involuntary SHE activation - (SHE man. call point or detector had not been activated):
- incorrect line termination (ER) in the SHE man. call point (correct value 10k Ohm)
- shortcircuit in the triggering circuit of the SHE-man. call point or autom. detector