Description of operating
SHE control panel TRZ Basic 4A/UP
Manual activation in case of fire/smoke/alarm
Smoke heat extraction / opening windows
Press the red OPEN switch
at a SHE manual call point, the windows open completely, the red LED display
-
SHE activated - is shining at all SHE manual call points, the ventilation function is out of order.
Smoke heat extraction / closing windows
Press the switch “closed”
at a SHE manual call point, the windows are closing, the red LED display
- SHE
activated - goes out at all SHE manual call points, the ventilation function is working again.
Note
: there is no reset of the connected and activated automatic detectors!
Automatic activation in case of fire/smoke/alarm
(if automatic detectors are connected only)
Smoke heat extraction / opening windows
Smoke reaches the automatic detectors, the windows are opened completely, the red display in the automatic detector
is shining, the red LED display
- SHE activated - is shining at all SHE manual call points, the ventilation function is
out of order.
Smoke heat extraction / closing windows
Press the switch “closed”
at a SHE manual call point, the windows are closing, the red LED display
- SHE
activated - goes out at all SHE manual call points, the yellow LED display
- malfunction - flashes.
Note
: there is no reset of the connected and activated automatic detectors!
Reset of automatic detectors
Set the automatic detectors free from smoke by blowing out or replace them in case of heavy soiling.
Press the RESET switch on the basic circuit control board of the control panel, the windows are closing, the red display
in the automatic detectors goes out, the red LED display
- SHE activated - goes out at all SHE manual call points,
the yellow LED display
- malfunction - goes out, the ventilation function is working again.
Daily ventilation
(if vent switches are connected only)
Opening windows
Press the switch “open” at the vent switch, the windows open completely. (Interruption of the opening by pressing both
switches together (Open and Closed) = STOP or by Stop switch depending on vent switch).
Closing windows
Press the switch “closed” at the vent switch, the windows close completely. (Interruption of the opening by pressing both
switches together (Open and Closed) = STOP or by Stop switch depending on vent switch). In case of mains or battery
failure, the windows close immediately.
Automatic ventilation control
If activated (see start up procedure), the windows are closing automatically after 10 min., in case of mains or battery
failure, the windows close immediately.