Start up procedure and trial run
Without mains voltage and without battery
Check all parts mechanically and electrically for fully tightened screw connections and damage, the terminals: plug in
connectors for motors and control elements as well as, if available, automatic detectors and wind/rain detectors.
Do not plug in the battery fuse!
With mains voltage and battery
Switch on mains. Plug in battery fuse.
Visual display in the control panel door
Max. 100 secs. after plugging in of the battery fuse and switching on of mains, check:
green LED
OK
- Operation OK - lit up,
red LED
- SHE activation - not lit up,
yellow LED
- Malfunction - not lit up.
Note
: In case of malfunction, see chapter “Troubleshooting” and “Fault finding”.
Vent switch (when existing)
Standard function, jumper J1 is not plugged
. Press switch “open”, the drives open the windows completely up to the end
position, the display “ventilation open” (when existing) is shining, observe the windows during this running.
Attention:
Make sure the drives can move freely at any times without obstruction. Pay attention to potential
collision, tension and crushing during this movement, too. Check the connection cables of the drives: they must
not be strained by tension or crushing.
Press the vent switch “closed”, the drives close the windows. The display “ventilation open” goes out. Press STOP during
running (STOP = press both switches “open” and “closed” at the same time), the drives stop. The display “ventilation
open” is shining. Repress vent switch “closed”, the drives run to close, the display “ventilation open” goes out. The drives
close the windows completely up to end position, the display “ventilation open” is not shining.
Attention:
Pay attention to potential collision, tension and crushing during this movement, too.
Ventilation “special function”
Suitable to connect key vent switches to insure the Stop-function.
Jumper J1 is plugged in. Press the switch “open”, the windows open. To stop the drives, press briefly the switch “closed”.
Repress the switch “closed”, the drives close the windows. To stop the drives, press briefly the switch “open”. Press the
switch “open” the windows open. Press/hold the switch “closed”, the drives close the windows. Press/hold the switch
“open”, the drives open the windows.
SHE manual call points
Press SHE OPEN switch briefly, the windows open completely. The red LED display
- SHE activated - lights up.
The green display
OK
- Operation OK - lights up. Press switch CLOSED of the vent switch, no drive reaction.
Press the switch “closed”
of the SHE manual call point. The windows close completely. The red LED display
"SHE activated” goes out. The green display
OK
“operating OK” is shining. Press the switch SHE “open”
the
windows open. During running, press the stop function of the vent switch, no reaction, the windows have to open. Press
the switch SHE “closed”
of the SHE manual call point, the windows close completely.
SHE control panel TRZ Basic 4A/UP