35
09/24999842
Technical datas
The power supplies and electrical control equipment are to be operated exclusively with the components authorised by
the manufacturer.
Electrical properties
Primary energy supply
Operating voltage supply:
230 V AC / 50 Hz, (±10 %), separately fused
Current consumption:
approx. 150 VA
Power consumption mains:
max. 1 A
Monitoring:
yes, Software monitoring
Terminal:
screw terminals max. 2.5 mm²
Fuse:
F1 mains fuse: T 1A H
Secondary energy supply
Batteries:
2 x 12 V / 2 Ah monitor funct. for low voltage wire breakage and fuse failure,
service
life
4
years
Battery type:
lead gel battery with VdS certifications
Emergency power:
72 h
Charging time:
20 h for emergency power
Terminal:
connecting cable and flat-pin plug
Monitoring:
yes,
cyclical
Fuse:
F3 battery fuse: FKS 5A
Output
Voltage:
24 V DC (nominal) (-15 % / +25 %), filtered
Ripple:
<1
Power (nominal):
4 A 10 % ED (referring to 30 min)
Power (temporary):
2.6 amp (≤600 ms)
Opening / closing sequence:
reversal of voltage polarity
Pause time during change of
polarity:
200
ms
Timing in accordance with
prEN 12 101-9:
yes, alteration of direction of travel every 2 min
Automatic activation:
after 3 min
Cable monitoring function:
linear drives (with 3rd monitoring lead combined with monitoring diodes)
Terminal:
max. 1.5 mm², screw terminal
Fuse:
F2 motor fuse, FKS 5A
Call point output
Voltage:
24
V
nominal
Power:
max. 60 mA, 100 % ED
Terminal:
max. 1.5 mm², screw terminal
max.
Pieces:
10
Emergency power:
yes
Automatic alarm unit output
Voltage:
24
V
nominal
Power:
max. 150 mA, 100 % ED
Terminal:
max. 1.5 mm², screw terminal
Cable monitoring function:
end resisted 10k
max.
Pieces:
6
Emergency power:
yes
SHE control panel TRZ Basic 4A/UP