SSD6000W2
19
● DSE 3110 not showing Volts or Hz running?
● Check the fuel pump is receiving 12V DC and
is operating - Replace if necessary.
Contaminated Fuel
● If possible run the generator from a separate
fuel source from the fuel tank.
The DSE 3110 is displaying the correct no-load frequency (approx.
52.5Hz
) but the
generator shuts down with the
Low AC Voltage
shutdown icon is displayed only.
Capacitor
● Test and/or replace the AC alternator
capacitor.
Main AC Alternator
● AC alternator tests would be advisable.
Fuel Lift Pump (12V DC)
Low AC Voltage
and
Low Hz/Frequency
could indicate the engine is running too
slow.
Warning
- It is not recommended to adjust the engine speed unless absolutely
necessary.
Low
Hz/Frequency
Shutdown
Low AC Voltage
Shutdown
A closer inspection of the engine would be advised e.g. check engine speed, replace
the injector etc.
Fuel Filter
● Check in-line fuel filter and replace if
necessary.
Fuel Hoses
● Check the condition of the fuel hoses from
the generator to the fuel tank.
Air Filter
● Check the condition of the air filter - Replace
if necessary.
The no-load frequency/rpm should measure approximately
52.5Hz/3150rpm
● Check the green plug with a brown & blue
wire is not loose.
2A Reset Button
●
Check for continuity and wiring on the reset
button - Replace if necessary.
Main AC Alternator
● Check or replace capacitor - AC alternator
tests would be advisable.
Emergency Stop Button
● Check if the emergency stop button has been
activated.
● Check the switches function and wiring on
the back of the emergency stop.
● If possible run the generator from a separate
fuel source from the fuel tank.
If none of the above solve the issue then a closer inspection of the engine would be
advised e.g. injector etc.
Engine Starting/Running Then Stopping 3 Times
Emergency Stop
Possible Cause
Check
DSE 3110 Control Module
● Check that all the green plugs are fitted
correctly and the wiring.
● Start and run the generator and measure the
AC voltage across the brown & blue wires -
approx. measurment: 230V AC.
DSE 3110 Control Module
Fail to Start
Is activated after
three attempts
to start.
Fault Icon
Air Filter
● Check the condition of the air filter - Replace
if necessary.
Contaminated Fuel