SSD6000W2
18
●
Check the condition of the battery leads.
cont.
20A Reset Button
●
Check for continuity and wiring on the reset
button - Replace if necessary.
Negative / Ground Connections
● Check No.1 wires on the control panel and
engine DC loom(s) have a sound connection to
battery negative.
Fuel Solenoid
● Check the fuel solenoid is receiving 12V DC
and is operating - Replace if necessary.
Fuel Lift Pump (12V DC)
Fault Finding - DSE 3110
Most common faults can be Identified by the fault icon displayed on the right hand side of the LCD screen.
The table below shows a fault description and/or the relevant icon together with a possible cause and checks
related to the fault icon displayed.
Fault Icon
Possible Cause
Check
Engine Not Starting/Running
●
Check the battery voltage, should be around
12.5V DC - Charge or Replace.
Starter Motor
●
Check the operation and wiring of the starter
motor - Replace if necessary.
Battery
If the battery needs charging or replacing, check the battery is being charged when
the generator is running -
See
-
Battery Charge System Fault Finding.
● Check the fuel pump is receiving 12V DC and
is operating - Replace if necessary.
● Check in-line fuel filter and replace if
necessary.
Emergency Stop Button
● Check the operation of the switches on the
back of the emergency stop button.
● Check the plugs on the DSE 3110, wiring and
output operation for the relays - Ref. diagram.
DSE 3110 Control Module
Fail to Start
Is activated after
three attempts
to start.
Before Fault Finding
Fault Finding
WARNING
- Please be aware of the potential hazards when working on a generator. Most basic fault finding
can be completed with ease. Other aspects of fault finding may require a trained technician to undertake to
ensure the safety to yourself and others.
Reference wiring diagram(s) in this handbook - The diagrams will be correct as to the time of printing.
Stephill reserve the right to change the wiring diagrams without prior warning.
We strongly advise before attempting any fault finding is to check the health of the generator battery. It
should measure around 12.4 to 12.6 Volts DC while the generator is at standstill.
Be aware of the service/maintenance schedule of the engine, ensuring the fuel filters are replaced regularly
along with the oil topped up and oil filter etc. - See -
Service and Maintenance
Before carrying out any checks ensure all
Load
is unplugged from the generator and be aware of any
potential exposed
Live
terminals while the generator is running! All checks and tests should only be carried
out by a competent engineer.