45
742.110 | 14.50
EN
15
Technical data
15.1
Controller
Inputs/outputs
Rated voltage (system voltage)
115 ... 230 V~, 50/60 Hz
Own consumption
≤ 0.8 W, two Pt1000 temperature sensors connected
Output R1
Quantity
Type
Switching current
Voltage
1
TRIAC
1.1 (1.1) A each
115 ... 230 V~, 50/60 Hz
Signal inputs/outputs
Signal inputs 1 ... 5
Quantity
Type of signal inputs 1 ... 4
Type of signal input 5
5
Pt1000 (temperature acquisition)
Pt1000 (temperature acquisition)
or
Pulse water meter using 1 gal/pulse, 2 gal/pulse,
5 gal/pulse, 10 gal/pulse, 1 l/pulse, 10 l/pulse, 25 l/pulse
(flow rate acquisition)
Signal output 0–10 R1
Type
Min. working resistance
0 ... 10 V
10 kΩ
Hydraulic schemes (systems)
Quantity
2
Display
Type
LCD display with backlighting
Application conditions
Degree of protection
IP22, DIN 40050 [without front panel: IP20]
Protection class
I
Ambient temperature
32 ... +122 °F, when wall-mounted
Physical specifications
Dimensions L x W x H
110 x 160 x 51 mm (4.33 x 6.30 x 2.01 inch)
Weight
350 g (0.77 lbs)
Software class
A
Type of action
type 1.Y
Type of fastening for permanently
connected cables
type X
Degree of pollution
2
Ball pressure test temperature
Casing pan: 257 °F
Other casing parts: 167 °F
Overvoltage category
class II (2500 V)
Tab. 8: Controller technical data
Содержание TR-A501T-U
Страница 47: ...47 742 110 14 50 EN 18 Notes ...