14.2 

AC cables and line circuit breakers

Inverter

AC cable conductor cross-section Line circuit breaker

StecaGrid 8000+ 3ph

5 x 1.5 mm²

3 x B16

5 x 2.5 mm²

3 x B16 or 3 x B25

5 x 4.0 mm²

3 x B16 or 3 x B25

StecaGrid 10 000+ 3ph 5 x 2.5 mm²

3 x B20

5 x 4.0 mm²

3 x B25

Tab. 12:  Conductor cross-sections of the AC cables and suitable line circuit breakers

14.3 

Table of countries

Details on setting the country are provided in Section 8.8, p. 62.

 

 Note

The requirements for the country-specific grid parameters may change at short notice. Contact the 

Steca Customer Service if the parameters specified below no longer correspond to the legally pre-

scribed requirements in your country. See Section 

Contact

, p. 80. 

Country

Reconnec

-

tion time

Voltage disconnection 

values (peak values) 

2)

Voltage disconnection 

values (average values) 

3)

Frequency discon-

nection values 

4)

upper

lower

upper

lower

upper

 8)

lower

Name

Display 

1)

s

%

s

%

s

%

s

%

s

Hz s Hz s

Germany 

5)

4900 Deutschland

60 15.0

0.2 –20.00 0.20

10 600.0

– 1.5 0.2 –2.5 0.2

Sweden

4600 Sverige

30 15.0

0.2 –15.00 0.20

6

60.0

–10 60.0 1.0 0.5 –3.0 0.5

France

3300 France

30 15.0

0.2 –15.00 0.20

10 600.0

– 0.2 0.2 –2.5 0.2

Portugal

35100 Portugal

20 15.0

0.2 –15.00 1.50

– 1.0 0.5 –3.0 0.5

Spain

3400 España

180 10.0

0.2 –15.00 0.20

– 1.0 0.2 –1.0 0.2

The Netherlands

3100 Nederland

30 10.0

2.0 –20.00 2.00

– 1.0 2.0 –2.0 2.0

Belgium_1 

6)

3200 Belgique 1

30 10.0

0.1 –50.00 0.10

–15

1.5 0.5 0.1 –2.5 0.1

Belgium_1 unlimited

3201 Belgique 1 unl

30 10.0

0.1 –50.00 0.10

–15

1.5 0.5 0.1 –2.5 0.1

Belgium_2 

6)

3202 Belgique 2

30 15.0

0.2 –20.00 0.20

10 600.0

– 0.5 0.2 –2.5 0.2

Belgium_2 unlimited

3203 Belgique 2 unl

30 15.0

0.2 –20.00 0.20

10 600.0

– 0.5 0.2 –2.5 0.2

Austria

4300 Österreich

30 15.0

0.2 –20.00 0.20

12 600.0

– 1.0 0.2 –3.0 0.2

Italy_1

3900 Italia 1

30 20.0

0.1 –20.00 0.20

– 0.3 0.1 –0.3 0.1

Italy_2

3901 Italia 2

30 20.0

0.1 –20.00 0.20

– 1.0 0.1 –1.0 0.1

Italy_3

3902 Italia 3

30 22.0

0.1 –25.00 0.20

– 5.0 0.2 –3.5 0.2

Slovenia

38600 Slovenija

30 15.0

0.2 –15.00 0.20

11

1.5

– 1.0 0.2 –3.0 0.2

Czech Republic

42000

Česko

30 15.0

0.2 –15.00 0.20

10 600.0

– 0.5 0.2 –0.5 0.2

Greek Islands

3001 Greece islands

180 15.0

0.5 –20.00 0.50

10 600.0

– 1.0 0.5 –2.5 0.5

Greek Mainland

3000 Greece continent

180 15.0

0.5 –20.00 0.50

10 600.0

– 0.5 0.5 –0.5 0.5

Australia 

6)

6100 Australia

60 17.0

2.0 –13.00 2.00

– 5.0 2.0 –3.5 2.0

Turkey

9000 Türkiye

30 15.0

0.2 –20.00 0.20

10 600.0

– 0.2 0.2 –2.5 0.2

Ireland

35300 Éire

30 10.0

0.5 –10.00 0.50

– 0.5 0.5 –2.0 0.5

United Kingdom G83

4400 United Kingdom G83 180 14.7

1.5 –10.00 1.50

– 0.5 0.5 –3.0 0.5

United Kingdom G59

4401 United Kingdom G59 180 15.0

0.5 –20.00 0.50

10

1.0

–13

2.5 0.1 0.5 –2.5 0.5

Switzerland

4100 Suisse

30 15.0

0.2 –20.00 0.20

10 600.0

– 0.2 0.2 –2.5 0.2

Hungary

3600 Magyarország

30 35.0

0.1 –50.00 0.10

10

2.0

–15

2.0 1.0 0.2 –1.0 0.2

Denmark_unlimited

4500 Danmark unlimited

60 15.0

0.2 –20.00 0.20

10 600.0

– 1.5 0.2 –2.5 0.2

Denmark 

7)

4500 Danmark

60 15.0

0.2 –20.00 0.20

10 600.0

– 1.5 0.2 –2.5 0.2

EN 50438 

50438 EN 50438

20 15.0

0.2 –15.00 1.50

– 1.0 0.5 –3.0 0.5

Bulgaria

3590 Bâlgarija

30 15.0

0.2 –20.00 0.20

10 600.0

– 0.2 0.2 –2.5 0.2

Mauritius

23000 Mauritius

180 10.0

0.2 –6.00 1.50

6

1.5

– 1.0 0.5 –3.0 0.5

Tab. 13:  Table of countries

1)

  Country code and name as shown on the display.

2)

  Disconnection values are upper and lower deviations from the peak values of the rated voltage 

78

744.378 | 12.13

EN

Содержание StecaGrid 10 000+ 3ph

Страница 1: ...744378 12 13 StecaGrid 8000 3ph StecaGrid 10000 3ph Installations und Bedienungsanleitung Installation and operating instructions Notice d installation et d utilisation 744 378 Z02 12 13 DE EN FR...

Страница 2: ...ng the DC connections 60 8 5 Preparing an additional ground connection 60 8 6 Preparing the data connection cable 61 8 7 Connecting the inverter and switching on the AC power 61 8 8 Initial commission...

Страница 3: ...xible connection Due to the wide input voltage range and a high input current all commonly available crystalline solar modules can be connected to the inverters in various configurations Beyond this t...

Страница 4: ...he inverter Type plate 1 2 9 4 6 3 5 7 8 Voltage 350 700V max 845V Current max 32A Voltage 3x400V 50Hz Current max 16A Power max 10300W 10000W for setting Belgium IP classification IP 54 DC Input AC O...

Страница 5: ...ioning visible damage including at the front operating panel smoke etc Cables Solar modules The photovoltaic system must not be switched on again until The device has been repaired by a dealer or the...

Страница 6: ...n and operating instructions Notice d installation et d utilisation 744 378 Z0x 12 xx DE EN FR Fig 4 Scope of delivery 5 Proper usage The inverter may only be used in grid connected photovoltaic syste...

Страница 7: ...power supply cables 6 3 Markings 6 3 1 Symbols Tab 2 describes the symbols used in this manual and on the device Symbol Description Location Symbol Description Location General danger warning Manual D...

Страница 8: ...2 Display monochrome 128 x 64 pixels 1 3 Type plate warning notices 1 4 Operating buttons ESC SET from left to right 1 5 Front panel with mechanical protection 1 6 1x AC connection 7 DC circuit breake...

Страница 9: ...ical value starts flashing and can be changed adopts a change changes the state of a control element check box radio button Press longer 1 second answers a query dialog with Yes navigates 1 step forwa...

Страница 10: ...t displayed at night solar irradiation too low example in fig left The CO2 savings shown in the status display are calcu lated using the savings factor 508 g kWh Menu 2 1 Designation of the main subme...

Страница 11: ...he Information menu item contains the following sub menu items Contact info System info see fig left Product designation Serial number of the inverter Information on the software and hardware versions...

Страница 12: ...n black Scroll bar Dialogs 3 2 2 1 Dialog heading A question presented to the user Response possibilities Back cancel Press ESC Confirm answer the question with Yes press and hold SET for 1 second Num...

Страница 13: ...e inverter Power reduction Derating cause of the power reduc tion Day max power the maximum power supplied in the current day 2 Abs max power the maximum power ever fed into the grid 2 Day max yield t...

Страница 14: ...es Arrow symbol Overexcitation Arrow symbol Underexcitation Technical details Each characteristic curve is defined by 2 to 8 nodes A node is defined by the output power P of the inverter x axis and th...

Страница 15: ...ons notes Some of this data can be sent to the devices listed under 7 7 3 7 7 2 Logged data The inverter stores the following data permanently in internal memory EEPROM Error conditions notes Energy y...

Страница 16: ...rid Vision First inverter Inverter Last inverter terminated Data cable supplied with the device Data cable supplied with the device or alternative data cable 7 7 4 Alternative data connection cable No...

Страница 17: ...lug 7 7 6 Addressing Every inverter must be assigned its own unique address for the communication between the bus master and slaves to function correctly see also 7 7 3 Every inverter is set with an a...

Страница 18: ...come loose accidentally When laying cables ensure that no damage occurs to any of the constructional fire safety meas ures in the building Make sure that no inflammable gases are present Observe all a...

Страница 19: ...the mounting surface with the attachment area for the inverter casing facing upwards Hanging the inverter on the mounting rail 3 2 4 1 5 6 Caution Danger of personal injury The inverter weighs 42 kg A...

Страница 20: ...3 3 Residual current circuit breaker Unless otherwise specified by the local installation regulations installation of an external Type A residual current circuit breaker is sufficient 8 3 4 Isolation...

Страница 21: ...tacts for the DC connections to the DC cable observing the correct polarity The DC connections are internally interlinked to one MPP tracker This means that external string fuses in their own casing m...

Страница 22: ...ons of the inverter until they audibly click into place 3 Insert the AC plug into the socket on the inverter until it audibly clicks into place 4 Seal the AC connection as required To do this feed the...

Страница 23: ...istic curve if prescribed for the selected country Setting the country The following applies when setting the country The country set must always be the same as the country where the inverter is insta...

Страница 24: ...ress SET briefly The day flashes 5 Press to change the day 6 Press SET briefly The change is adopted 7 Press The month is selected 8 Repeat steps 4 to 6 for the month 9 Press The year is selected 10 R...

Страница 25: ...9 7 Press SET briefly The setting value flashes 8 Press to change the number of nodes 9 Press SET briefly The value is adopted 10 Press SET for a longer time 11 Press to select a setting value for the...

Страница 26: ...d for a longer time then the inverter restarts anew and synchronises itself with the grid 8 9 Switching on the DC supply Set the DC circuit breaker on the inverter to position I Fig 12 After testing v...

Страница 27: ...subjected to sunlight Disconnecting the AC plug from the inverter 1 Remove the AC plug from the socket on the inverter as de scribed on p 123 onwards 2 Check that all pins of the AC plug are free of...

Страница 28: ...us Monthly yield Annual yield Time date Remuneration currency and amount kWh Time 2 Monthly yield Self test 3 2 2 2 Day yield Annual yield Total yield Output power Only shown when Measurements is sele...

Страница 29: ...call up the status display as required 2 Press SET The main menu is displayed with the top item selected 3 Press to select a menu entry 4 Press SET to call up the submenu fig left 5 Repeat steps 3 and...

Страница 30: ...f 2 Press SET The selected radio button is switched on and the previously switched on radio button is switched off 3 Press ESC The next higher menu level is displayed Changing numeric settings A numer...

Страница 31: ...hanged in the service menu The service menu must therefore only be used by professional personnel who know the applicable regulations and standards 1 Select the Service menu item 2 Press SET The fig s...

Страница 32: ...elf test is cancelled and the inverter displays the status message Self test failed The inverter remains disconnected from the grid relay open no feeding until the self test is passed successfully Not...

Страница 33: ...f test was not started or was cancelled due to insufficient sunlight especially in the evening at night Repeat the self test during the day when the inverter is feeding the grid Invalid grid condi tio...

Страница 34: ...or Type Error symbol The inverter has detected a serious error The inverter will not feed the grid while this error is present Please contact your installer More information on this is provided in Tab...

Страница 35: ...mum permissible value The inverter switches off due to legally prescribed requirements and waits for a prescribed time before switching on again If the fault remains present the inverter switches off...

Страница 36: ...ation openings on the upper and lower sides of the device are free of dust Clean the inverter when necessary as described below Notice Danger of damage to components Do not use especially the followin...

Страница 37: ...the country settings Rated output voltage 400 V Maximum output current 16 A Rated output current 11 6 A 14 3 A Maximum active power cos 1 8 800 W 1 3 10 300 W 2 3 Maximum active power cos 0 95 8 800...

Страница 38: ...ammonia solvents Equipment and design Degree of protection IP54 Overvoltage category III AC II DC DC connection Multi Contact MC4 4 pairs rated current of 22 A per input AC connection Type Wieland RS...

Страница 39: ...0 2 2 5 0 2 Belgium_2 unlimited 3203 Belgique 2 unl 30 15 0 0 2 20 00 0 20 10 600 0 0 5 0 2 2 5 0 2 Austria 4300 sterreich 30 15 0 0 2 20 00 0 20 12 600 0 1 0 0 2 3 0 0 2 Italy_1 3900 Italia 1 30 20...

Страница 40: ...5 year commercial guarantee to the specialist dealer from the date of invoice or receipt This voluntary guarantee applies only to products sold within an EU country The legal guarantee entitlements a...

Страница 41: ...Contact In the case of complaints or faults please contact the local dealer from whom you purchased the product They will help you with any issues you may have Europe Steca Elektronik GmbH Mammostrass...

Страница 42: ...121 744 378 12 13 Appendix Appendix Zertifikate Certificates Certificats...

Страница 43: ...122 744 378 12 13 Appendix...

Страница 44: ...123 744 378 12 13 Appendix Montage Installation Montage AC Stecker AC plug connecteur AC...

Страница 45: ...124 744 378 12 13 Appendix...

Страница 46: ...125 744 378 12 13 Appendix Wechselrichter Inverter Onduleur 228 5 StecaGrid 10 000 200 mm 625 mm 795 mm 250 mm 200 mm 302 mm 744 340 Z01 228 5 StecaGrid 10000 200 mm 300 mm...

Страница 47: ...744378...

Отзывы: