Setting the country and reactive power characteristic curve
Note
The country can only be set once!
1. Press
to select a country.
2. Press
SET
briefly.
3. Press
SET
for a longer time.
If a reactive power characteristic curve is not prescribed
for the selected country then finish initial commission-
ing (see
Finishing initial commissioning
).
4. Press
to select the reactive power characteristic
curve according to the local regulations.
5. Press
SET
briefly. The characteristic curve is adopted.
6. Press
SET
for a longer time.
–
If
Default
char
.
curve
was selected in step 4 then
continue with step 18.
–
If
Char
.
curve
cos
φ
=
1
was selected in step 4 then
continue with step 19.
7. Press
SET
briefly. The setting value flashes.
8.
Press
to change the number of nodes.
9. Press
SET
briefly. The value is adopted.
10. Press
SET
for a longer time.
11. Press
to select a setting value for the first node.
P%
has predefined fixed values for the first and last node
(000%, 100%).
12. Press
SET
briefly. The setting value flashes.
13. Press
to change the value.
14. Press
SET
briefly. The change is adopted.
15. Repeat steps 11 to 14 for the other setting value as
required.
16. Press
SET
for a longer time.
17. Repeat steps 11 to 16 for the setting values of the re-
maining nodes.
18. Press
to select the maximum overall apparent out-
put power
1)
of the system (!).
1)
Total of the maximum apparent output power values
of all inverters of the system.
19. The characteristic curve is displayed graphically (example
in fig. left).
20. Press
SET
for a longer time.
64
744.378 | 12.13
EN
Содержание StecaGrid 10 000+ 3ph
Страница 42: ...121 744 378 12 13 Appendix Appendix Zertifikate Certificates Certificats...
Страница 43: ...122 744 378 12 13 Appendix...
Страница 44: ...123 744 378 12 13 Appendix Montage Installation Montage AC Stecker AC plug connecteur AC...
Страница 45: ...124 744 378 12 13 Appendix...
Страница 47: ...744378...