StecaGrid 8000+ 3ph

StecaGrid 10 000+ 3ph

Efficiency values (at 5%, 10%, 20%, 

25%, 30%, 50%, 75%, 100% of the 

rated power) at maximum MPP voltage

74.1%, 92.7%, 94.8%, 

95.5%, 95.7%, 96.2%, 

95.8%, 95.3%

77.2%, 94.1%, 95.3%, 

95.7%, 95.9%, 96.2%, 

95.9%, 95.3%

Efficiency reduction in the case of 

deviation from the DC rated voltage

–0.0025%/V

Power derating at full power

from +50 °C (T

amb

)

Switch-on power

80 W

Switch-off power

20 W

Standby power

9 W

Safety

Protection class

I

Isolation principle

no galvanic isolation, transformerless

Grid monitoring

MSD, compliant with DIN VDE 0126-1-1 and VDE AR N 4105

Isolation monitoring

yes, integrated

Residual current monitoring

yes, integrated 

5)

Overvoltage protection version

varistors

Application conditions

Area of application

indoor rooms with or without air conditioning, outdoors 

with protection

Corrosion categories

C3

Ambient temperature range T

amb

–20 °C … +60 °C

Storage temperature

–30 °C ... +80 °C

Relative humidity

0% ... 95%, non-condensing

Installation elevation

≤ 2000 m above sea level

Degree of pollution

PD3

Noise emission

< 60 dBA

Impermissible ambient gases

ammonia, solvents

Equipment and design 

Degree of protection

IP54

Overvoltage category

III (AC), II (DC) 

DC connection

Multi-Contact MC4 (4 pairs), rated current of 22 A per input

AC connection

Type

Wieland RST25i5 plug

Connection conductor cross-section

cable cross-sections ≤ 4 mm

2

,  

cable diameters 10 ... 14 mm

2

,

cable diameters 15 ... 18 mm

2

 with optionally available AC 

plug only

Opposing socket

included in delivery

Dimensions (X x Y x Z)

400 x 847 x 225 mm

Weight

42 kg

Display

graphical display, 128 x 64 pixels

Communication interface

RS485; 2 x RJ45 sockets; connection to StecaGrid Vision, 

Meteocontrol WEB'log, Solar-Log or StecaGrid Monitor

Feed-in management as per EEG 2012

EinsMan-ready, via RS485 interface

Integrated DC circuit breaker

yes, compliant with VDE 0100-712

Cooling principle

temperature-controlled fan, variable speed

Test certificate

clearance certificate as per DIN VDE 0126-1-1, CE symbol, 

VDE AR N 4105, G59, G83, AS4777, UTE C 15-712-1. 

under preparation: CEI 0-21

Tab. 11:  Inverter technical data

1)

  Germany and Denmark_unlimited: 8,000 W

2)

  Germany and Denmark_unlimited: 9,900 W

3)

  Denmark: 6,000 W

4)

  Denmark: 6,670 VA at cos 

φ

 = 0.90; 6,320 VA at cos 

φ

 = 0.95

5)

  The design of the inverter prevents it from causing DC leakage current. 

77

744.378 | 12.13

EN

Содержание StecaGrid 10 000+ 3ph

Страница 1: ...744378 12 13 StecaGrid 8000 3ph StecaGrid 10000 3ph Installations und Bedienungsanleitung Installation and operating instructions Notice d installation et d utilisation 744 378 Z02 12 13 DE EN FR...

Страница 2: ...ng the DC connections 60 8 5 Preparing an additional ground connection 60 8 6 Preparing the data connection cable 61 8 7 Connecting the inverter and switching on the AC power 61 8 8 Initial commission...

Страница 3: ...xible connection Due to the wide input voltage range and a high input current all commonly available crystalline solar modules can be connected to the inverters in various configurations Beyond this t...

Страница 4: ...he inverter Type plate 1 2 9 4 6 3 5 7 8 Voltage 350 700V max 845V Current max 32A Voltage 3x400V 50Hz Current max 16A Power max 10300W 10000W for setting Belgium IP classification IP 54 DC Input AC O...

Страница 5: ...ioning visible damage including at the front operating panel smoke etc Cables Solar modules The photovoltaic system must not be switched on again until The device has been repaired by a dealer or the...

Страница 6: ...n and operating instructions Notice d installation et d utilisation 744 378 Z0x 12 xx DE EN FR Fig 4 Scope of delivery 5 Proper usage The inverter may only be used in grid connected photovoltaic syste...

Страница 7: ...power supply cables 6 3 Markings 6 3 1 Symbols Tab 2 describes the symbols used in this manual and on the device Symbol Description Location Symbol Description Location General danger warning Manual D...

Страница 8: ...2 Display monochrome 128 x 64 pixels 1 3 Type plate warning notices 1 4 Operating buttons ESC SET from left to right 1 5 Front panel with mechanical protection 1 6 1x AC connection 7 DC circuit breake...

Страница 9: ...ical value starts flashing and can be changed adopts a change changes the state of a control element check box radio button Press longer 1 second answers a query dialog with Yes navigates 1 step forwa...

Страница 10: ...t displayed at night solar irradiation too low example in fig left The CO2 savings shown in the status display are calcu lated using the savings factor 508 g kWh Menu 2 1 Designation of the main subme...

Страница 11: ...he Information menu item contains the following sub menu items Contact info System info see fig left Product designation Serial number of the inverter Information on the software and hardware versions...

Страница 12: ...n black Scroll bar Dialogs 3 2 2 1 Dialog heading A question presented to the user Response possibilities Back cancel Press ESC Confirm answer the question with Yes press and hold SET for 1 second Num...

Страница 13: ...e inverter Power reduction Derating cause of the power reduc tion Day max power the maximum power supplied in the current day 2 Abs max power the maximum power ever fed into the grid 2 Day max yield t...

Страница 14: ...es Arrow symbol Overexcitation Arrow symbol Underexcitation Technical details Each characteristic curve is defined by 2 to 8 nodes A node is defined by the output power P of the inverter x axis and th...

Страница 15: ...ons notes Some of this data can be sent to the devices listed under 7 7 3 7 7 2 Logged data The inverter stores the following data permanently in internal memory EEPROM Error conditions notes Energy y...

Страница 16: ...rid Vision First inverter Inverter Last inverter terminated Data cable supplied with the device Data cable supplied with the device or alternative data cable 7 7 4 Alternative data connection cable No...

Страница 17: ...lug 7 7 6 Addressing Every inverter must be assigned its own unique address for the communication between the bus master and slaves to function correctly see also 7 7 3 Every inverter is set with an a...

Страница 18: ...come loose accidentally When laying cables ensure that no damage occurs to any of the constructional fire safety meas ures in the building Make sure that no inflammable gases are present Observe all a...

Страница 19: ...the mounting surface with the attachment area for the inverter casing facing upwards Hanging the inverter on the mounting rail 3 2 4 1 5 6 Caution Danger of personal injury The inverter weighs 42 kg A...

Страница 20: ...3 3 Residual current circuit breaker Unless otherwise specified by the local installation regulations installation of an external Type A residual current circuit breaker is sufficient 8 3 4 Isolation...

Страница 21: ...tacts for the DC connections to the DC cable observing the correct polarity The DC connections are internally interlinked to one MPP tracker This means that external string fuses in their own casing m...

Страница 22: ...ons of the inverter until they audibly click into place 3 Insert the AC plug into the socket on the inverter until it audibly clicks into place 4 Seal the AC connection as required To do this feed the...

Страница 23: ...istic curve if prescribed for the selected country Setting the country The following applies when setting the country The country set must always be the same as the country where the inverter is insta...

Страница 24: ...ress SET briefly The day flashes 5 Press to change the day 6 Press SET briefly The change is adopted 7 Press The month is selected 8 Repeat steps 4 to 6 for the month 9 Press The year is selected 10 R...

Страница 25: ...9 7 Press SET briefly The setting value flashes 8 Press to change the number of nodes 9 Press SET briefly The value is adopted 10 Press SET for a longer time 11 Press to select a setting value for the...

Страница 26: ...d for a longer time then the inverter restarts anew and synchronises itself with the grid 8 9 Switching on the DC supply Set the DC circuit breaker on the inverter to position I Fig 12 After testing v...

Страница 27: ...subjected to sunlight Disconnecting the AC plug from the inverter 1 Remove the AC plug from the socket on the inverter as de scribed on p 123 onwards 2 Check that all pins of the AC plug are free of...

Страница 28: ...us Monthly yield Annual yield Time date Remuneration currency and amount kWh Time 2 Monthly yield Self test 3 2 2 2 Day yield Annual yield Total yield Output power Only shown when Measurements is sele...

Страница 29: ...call up the status display as required 2 Press SET The main menu is displayed with the top item selected 3 Press to select a menu entry 4 Press SET to call up the submenu fig left 5 Repeat steps 3 and...

Страница 30: ...f 2 Press SET The selected radio button is switched on and the previously switched on radio button is switched off 3 Press ESC The next higher menu level is displayed Changing numeric settings A numer...

Страница 31: ...hanged in the service menu The service menu must therefore only be used by professional personnel who know the applicable regulations and standards 1 Select the Service menu item 2 Press SET The fig s...

Страница 32: ...elf test is cancelled and the inverter displays the status message Self test failed The inverter remains disconnected from the grid relay open no feeding until the self test is passed successfully Not...

Страница 33: ...f test was not started or was cancelled due to insufficient sunlight especially in the evening at night Repeat the self test during the day when the inverter is feeding the grid Invalid grid condi tio...

Страница 34: ...or Type Error symbol The inverter has detected a serious error The inverter will not feed the grid while this error is present Please contact your installer More information on this is provided in Tab...

Страница 35: ...mum permissible value The inverter switches off due to legally prescribed requirements and waits for a prescribed time before switching on again If the fault remains present the inverter switches off...

Страница 36: ...ation openings on the upper and lower sides of the device are free of dust Clean the inverter when necessary as described below Notice Danger of damage to components Do not use especially the followin...

Страница 37: ...the country settings Rated output voltage 400 V Maximum output current 16 A Rated output current 11 6 A 14 3 A Maximum active power cos 1 8 800 W 1 3 10 300 W 2 3 Maximum active power cos 0 95 8 800...

Страница 38: ...ammonia solvents Equipment and design Degree of protection IP54 Overvoltage category III AC II DC DC connection Multi Contact MC4 4 pairs rated current of 22 A per input AC connection Type Wieland RS...

Страница 39: ...0 2 2 5 0 2 Belgium_2 unlimited 3203 Belgique 2 unl 30 15 0 0 2 20 00 0 20 10 600 0 0 5 0 2 2 5 0 2 Austria 4300 sterreich 30 15 0 0 2 20 00 0 20 12 600 0 1 0 0 2 3 0 0 2 Italy_1 3900 Italia 1 30 20...

Страница 40: ...5 year commercial guarantee to the specialist dealer from the date of invoice or receipt This voluntary guarantee applies only to products sold within an EU country The legal guarantee entitlements a...

Страница 41: ...Contact In the case of complaints or faults please contact the local dealer from whom you purchased the product They will help you with any issues you may have Europe Steca Elektronik GmbH Mammostrass...

Страница 42: ...121 744 378 12 13 Appendix Appendix Zertifikate Certificates Certificats...

Страница 43: ...122 744 378 12 13 Appendix...

Страница 44: ...123 744 378 12 13 Appendix Montage Installation Montage AC Stecker AC plug connecteur AC...

Страница 45: ...124 744 378 12 13 Appendix...

Страница 46: ...125 744 378 12 13 Appendix Wechselrichter Inverter Onduleur 228 5 StecaGrid 10 000 200 mm 625 mm 795 mm 250 mm 200 mm 302 mm 744 340 Z01 228 5 StecaGrid 10000 200 mm 300 mm...

Страница 47: ...744378...

Отзывы: