Midilift XLplus
Maintenance Guide
Jan
2014
Issue
4
34
17.5 Set the lift to run at 80.0 Hz
17.6 Re set the lift to run at 50.0 Hz
Access upper landing floor
controller and activate stop
switch
The Inverter should be
flashing ’80.00’. Hold ‘v’ to
reach a value of ‘50.00’.
Press ‘FUNC/DATA’ once.
Display should read ‘F 0 0’
Use the ‘^’ and ‘v’ buttons to
display ‘F 0 3’. This function
allows us to alter the max
allowable frequency
Press ‘FUNC/DATA’ once to
display ’80.00’.
Hold ‘v’ to reach a value of
‘50.00’
Press ‘FUNC/DATA’ to save
value. ‘F 0 4’ should be
displayed.
Press ‘PROG/RESET’ twice
to display ’50.00’. Value
should be flashing in the
display.
Access upper landing floor
controller and activate stop
switch
Inverter should be flashing
50.0 Hz. Press ‘PRG/RESET
to display ‘I.F_ _’.
Press ‘FUNC/DATA’ once.
Display should read ‘F 0 0’
Use the ‘^’ and ‘v’ buttons
until ‘F 0 3’ is displayed. This
function allows the user to
alter the max allowable
frequency.
Press ‘FUNC/DATA’ once to
display ’50.00’.
Hold ‘^’ to reach a value of
‘80.00’.
Press ‘FUNC/DATA’ to save
value. ‘F 0 4’ should be
displayed.
Press ‘PROG/RESET’ twice to
display ’50.00’.
The inverter will now allow us
to increase the frequency to
80.Hz. Press and hold ‘^’ to
set the value to ’80.00’
Press ‘FUNC/DATA’ to save.
’80.00’ should be flashing in
the display.
The lift will now run at a higher
speed, allowing the user to
overspeed the lift.