Energy and Power Sources for Generating Steam
Spirax Sarco Compact Clean Steam Generators can be configured and manufactured to
use one (1) of two (2) possible energy sources for generating clean steam: (HTM 2031).
Steam:
Electricity
∆
Note: Most Spirax Sarco Compact Clean Steam Generators use steam as the
energy source for generating clean steam. Therefore, procedures detailed in this
manual will be geared towards the installation, operation, and maintenance of steam
powered units.
When procedures differ substantially for the installation, operation, and /or maintenance of
units powered with electricity, notes will be included giving specific instructions for those
units.
The following table lists the range of acceptable pressures and temperature at the inlet
for each energy source.
Energy source
Maximum Temperature °C /
Degree Centigrade
Maximum pressure
bar g
Steam
184°C
10 bar g
Electricity
Upon request
N/A
∆
Note: Consult the design specifications for the unit, as well as the nameplate
attached to the exterior of the pressure vessel and individual specification tags on
pressure related components and controls, for design specifications and maximum
pressure for the unit.
Controls
Spirax Sarco Steam Generators are equipped with both electronically and pneumatically
activated controls to regulate pressure (temperature) and water level. The electronic
PLC control panel used, depending on individual design specifications, has a power
requirement of 380 volt three phase. Pneumatic controls, depending on individual design
specifications, require instrument air pressures of 8 bar g (120 psi). Consult the individual
design specifications for the unit and controls for the exact requirements.
Construction
All Spirax Sarco Compact Clean Steam Generators are constructed from superior materials
and utilize only the highest quality components. All parts in contact with generated steam
are S.S. 316L. Each Compact Steam Generator meets or exceeds all applicable V.S.R
code (Vessel Security Rules) regulations and are built to conform to 97/23/CE Directive.
Each Spirax Sarco Compact Clean Steam Generator is equipped with a
approved
safety valve and an external drain, providing a means to remove accumulated sediment.