42
3. If the pump is not completely drained, hot water may be discharged.
4. Disconnect the wires leading from/to the electric cabinet.
5. Disconnect the bolts.
6. Continue loosening the connections until the pump can be removed.
7. Examine the pump for damage or incorrect positioning. For the exact procedure for
examination refer to the Spirax Sarco manual information included with the unit.
8. To install a new pump, align with the feed lines and start the fittings. Follow
recommendations contained in the documentation.
9. After ensuring that the pump is correctly aligned, tighten the fittings.
10. Follow the start-up procedures (page 21) to put the unit back on-line. Carefully check
all connections for any sign of leakage.
Fig. 26
Water pump