056357/B
RAC
5-2
Electrical Installation
Rudder Angle Feedback Unit Potentiometer
Generally, a dedicated rudder angle feedback unit will be installed for
the RAC. Alternatively, one or more RACs may use a separate
potentiometer in a feedback unit which also contains potentiometers
for, e. g., other RAI systems or the VDR.
WARNING
Risk of injury
Connecting the Rudder Angle Calibrator to a rudder angle feedback unit
in parallel with the steering gear feedback loop bears the risk of malfunc-
tion of the steering gear in case of wire breaks or short-circuits resulting
in possible injury and/or damage.
Under no circumstances must the RAC be connected to a rudder angle
feedback unit potentiometer in parallel with the steering gear feedback
loop.
CAUTION
A
Risk of damage
As the feedback potentiometer supply voltage is provided by the Rudder
Angle Calibrator, connecting the RAC to a feedback potentiometer in par-
allel to any device other than a second RAC bears the risk of damage in
case of wire breaks or short-circuits.
Never connect the RAC to a feedback potentiometer in parallel to any
device other than a second RAC.
Содержание Rudder Angle Indicator System
Страница 18: ...056357 B RAIS 1 10 Declaration of Conformity...
Страница 20: ...056357 B RAIS 2 2 Normal Operational Mode...
Страница 26: ...056357 B RAIS 3 6 Viewing RAC Errors through SUSI...
Страница 28: ...056357 B RAIS 4 2 Maintenance by Service Personnel...
Страница 58: ...056357 B RAIS 7 4 General Troubleshooting Instructions...
Страница 64: ...056357 B RAIS 8 6 Replacing Alarm Output Relays...
Страница 95: ......
Страница 96: ......
Страница 97: ......
Страница 98: ......
Страница 99: ......
Страница 100: ......
Страница 101: ......
Страница 102: ......
Страница 103: ......
Страница 104: ......
Страница 105: ......
Страница 106: ......
Страница 107: ......
Страница 108: ......
Страница 109: ......
Страница 110: ......
Страница 111: ......
Страница 112: ......
Страница 113: ......
Страница 114: ......
Страница 115: ......