Motor Controller 6 AC KNX DRM
30.11.2020
Ref. 5157011A
22/
26
6.4.3 Block manual tilt/stops orders
Default value:
No
Selection options:
No
Yes
This parameter can be used to block step/stop and tilting orders (bit) via the object (67-72). If a telegram with
value "1" is received by the corresponding object while the blind is tilting, this tilting operation will be com-
pleted. Only then will further tilting orders (bit) be blocked. If a telegram with value "0" is received by the cor-
responding object, the step/stop orders (bit) will be allowed again.
6.4.4 Block manual orders and IP 1
Default value:
No
Selection options:
No
Yes
This parameter allows Up/Down position orders (bit) to be blocked via the object (67-72). If a telegram with
value "1" is received by the corresponding object while the blind is moving, this operation will be completed.
Only then will further Up/Down orders (bit) be blocked. If a telegram with value "0" is received by the corre-
sponding object, the Up/Down orders (bit) will be allowed again.
6.4.5 Reaction at main power return (230 V) (for all motors)
Default value:
Ignore
Selection options:
Upper end limit
Lower end limit
Ignore
Close window
Open window
Stop
This parameter determines the position which will be adopted when the mains power (230 V) returns.
6.4.5.1 Reaction at bus power failure
Default value:
Ignore
Selection options:
Upper end limit
Lower end limit
Ignore
Close window
Open window
Stop
This parameter determines the position which will be adopted in the event of a bus power failure.
6.4.6 Feedback upper/lower end limit
Default value:
No
Selection options:
No
Yes
This option opens the "
Position feedback mode” parameter.