Motor Controller 6 AC KNX DRM
30.11.2020
Ref. 5157011A
9/
26
No.
Object designation
Type
DPT_ID Description
37
Motor 1 Move to IP 1
1 Bit
1.008
If a telegram with the value "1" is received by one
of these communication objects, the corresponding
blind moves to intermediate position 1 configured in
the ETS software. If a telegram with the value "0" is
received by one of these communication objects,
the corresponding blind moves to the upper end
limit.
(Manual command)
38
Motor 2 Move to IP 1
1 Bit
1.008
39
Motor 3 Move to IP 1
1 Bit
1.008
40
Motor 4 Move to IP 1
1 Bit
1.008
41
Motor 5 Move to IP 1
1 Bit
1.008
42
Motor 6 Move to IP 1
1 Bit
1.008
43
Motor 1 Move to IP 2
1 Bit
1.008
If a telegram with the value "1" is received by one
of these communication objects, the corresponding
blind moves to intermediate position 2 configured in
the ETS software. If a telegram with the value "0" is
received by one of these communication objects,
the corresponding blind moves to the upper end
limit.
(Automatic command)
44
Motor 2 Move to IP 2
1 Bit
1.008
45
Motor 3 Move to IP 2
1 Bit
1.008
46
Motor 4 Move to IP 2
1 Bit
1.008
47
Motor 5 Move to IP 2
1 Bit
1.008
48
Motor 6 Move to IP 2
1 Bit
1.008
49
Motor 1 IP 1 Save/Delete
1 Bit
1.002
If a telegram with the value "1" is received by one
of these communication objects, the current posi-
tion of the corresponding blind is saved as interme-
diate position 1
If a telegram with the value "0" is received by one
of these communication objects, intermediate posi-
tion 1 is deleted.
50
Motor 2 IP 1 Save/Delete
1 Bit
1.002
51
Motor 3 IP 1 Save/Delete
1 Bit
1.002
52
Motor 4 IP 1 Save/Delete
1 Bit
1.002
53
Motor 5 IP 1 Save/Delete
1 Bit
1.002
54
Motor 6 IP 1 Save/Delete
1 Bit
1.002
55
Motor 1 Security low prio
1 Bit
1.001
If a telegram with the value "1" is received by one
of these communication objects, the corresponding
blind moves to the position configured in the ETS
software (security, low priority). All other position
orders are blocked. If a telegram with the value "0"
is received by one of these communication objects,
the security is disabled and position orders can
once again be received. If "Repeat last position or-
der after security (Yes)" is selected in the ETS pa-
rameters, the blind moves to the position it was in
before the security function was enabled.
If a telegram with the value "1" is received by one
of these communication objects 61
–66 (security,
high priority), the corresponding blind moves to the
position configured in the ETS software (security,
high priority).
56
Motor 2 Security low prio
1 Bit
1.001
57
Motor 3 Security low prio
1 Bit
1.001
58
Motor 4 Security low prio
1 Bit
1.001
59
Motor 5 Security low prio
1 Bit
1.001
60
Motor 6 Security low prio
1 Bit
1.001