5 Communication objects
5.1 Overview of the objects
A maximum of 114 communication objects are available: they can not, however, all be used at the same
time. In total, a maximum of 250 group addresses can be connected.
5.1.1 Object list
No.
Object designation
Type
DPT_ID Description
1
Motor 1 Up/Down
1 Bit
1.008
If a telegram with a value of "0" is received by this
communication object, the corresponding blind is
raised or the window is closed. If a telegram with a
value of "1" is received, the corresponding blind is
lowered or the window is opened. When the travel
time configured for the up and down direction ex-
pires, the output relays are disabled.
2
Motor 2 Up/Down
1 Bit
1.008
3
Motor 3 Up/Down
1 Bit
1.008
4
Motor 4 Up/Down
1 Bit
1.008
5
Motor 5 Up/Down
1 Bit
1.008
6
Motor 6 Up/Down
1 Bit
1.008
7
Motor 1 Step/Stop
1 Bit
1.007
For Venetian blinds:
If a telegram is received by one of these communi-
cation objects when a Venetian blind is moving, the
movement is stopped regardless of whether "0" or
"1" is received. If the Venetian blind is not moving,
a turn is performed. Furthermore, if a telegram with
the value "1" is received, the slats close and if a tel-
egram with the value "0" is received, they move up-
wards. The turn duration is determined in the pa-
rameter settings.
For vertical awnings, roller shutters, awnings
and windows:
If a telegram is received by one of these communi-
cation objects when one of the end devices is mov-
ing, the movement is stopped, regardless of
whether "0" or "1" is received. If a telegram is re-
ceived one of these communication objects and
one of the end devices is not moving, no operation
is performed.
8
Motor 2 Step/Stop
1 Bit
1.007
9
Motor 3 Step/Stop
1 Bit
1.007
10
Motor 4 Step/Stop
1 Bit
1.007
11
Motor 5 Step/Stop
1 Bit
1.007
12
Motor 6 Step/Stop
1 Bit
1.007
13
Motor 1 Position Up/Down
Automatic
1 Byte 5.001
If a telegram is received by one of these communi-
cation objects, the corresponding blind moves to
the position which is dependent on the value re-
ceived (%): "0" = upper end limit, "100" = lower end
limit.
For Venetian blinds: When the position is reached,
the slats are turned to the same position as they
were in before.
14
Motor 2 Position Up/Down
Automatic
1 Byte 5.001
15
Motor 3 Position Up/Down
Automatic
1 Byte 5.001
16
Motor 4 Position Up/Down
Automatic
1 Byte 5.001
17
Motor 5 Position Up/Down
Automatic
1 Byte 5.001
18
Motor 6 Position Up/Down
Automatic
1 Byte 5.001